'17 • KX-T-264
Error code
Remote control:
LED Green Red
Indoor
Outdoor
Content
E6
Indoor heat exchanger
temperature thermistor anomaly (Thi-R)
Keeps ashing
1-time ash
Keeps ashing
Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis Countermeasure
Is
the connector of
thermistor connected
properly ?
Regarding the characteristics of
the thermistor, see the following chart.
Are
the characteristics
of thermistor OK?
*1
NO
NO
YES
*1 Check several times to prove any poor connection
YES
T
emperarture thermistor resistance (kΩ
)
Temperature-resistance characteristics of indoor heat
exchanger temperature thermistor (Thi-R1, R2, R3)
5kΩ at 25ºC
Temperature (ºC)
Insert the connector
securely.
Replace thermistor.
(Thi-R)
Replace indoor unit control.
PCB
2. Error detection method
Detection of anomalously low
temperature (resistance)
of Thi-R1, R2, R3.
3
.
Condition of error displayed
If -40ºC or lower is
detected for 5 seconds
continuously, compressor
stops. After 3-minutes delay,
the compressor is restarted
automatically, but if this
anomaly occurs again within
60 minutes after the initial
detection.
Or if 70ºC or higher is
detected for 5 seconds
continuously.
4. Presumable cause
Anomalous connection
of indoor heat exchanger
temperature thermistor
Indoor heat exchanger
temperature thermistor
anomaly
Indoor unit control PCB
anomaly
Note: