'17 • KX-T-264
Error code
Remote control:
LED Green Red
Indoor
Outdoor
Content
E7
Indoor return air
temperature thermistor anomaly (Thi-A)
Keeps ashing
1-time ash
Keeps ashing
Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis Countermeasure
Is
the connector of
thermistor connected
properly ?
Regarding the characteristics of
the thermistor, see the following chart.
Temperature-resistance characteristics of indoor
return air temperature thermistor (Thi-A)
Are
the characteristics
of thermistor OK?
*1
NO
NO
YES
YES
*1 Check several times to prove any poor connection
15
10
5
0 10 30 40 20 50
T
emperature thermistor resistance (k
)
Tem
p
erature (°C)
5kΩ at 25°C
Insert the connector
securely.
Replace thermistor
(Thi-A).
Replace indoor unit control
PCB.
2. Error detection method
Detection of anomalously low
temperature (resistance) of
Thi-A.
3
.
Condition of error displayed
If -20°C or lower is
detected for 5 seconds
continuously, compressor
stops. After 3-minutes delay
the compressor is restarted
automatically, but if this
anomaly occurs again within
60 minutes after the initial
detection.
Or detected for 5 seconds
continuously.
4. Presumable cause
Anomalous connection of
indoor return air temperature
thermistor
Indoor return air temperature
thermistor anomaly
Indoor unit control PCB
anomaly
Note:
95