EasyManua.ls Logo

Mitsubishi FDTN508HES - Preset Point of the Protective Devices

Mitsubishi FDTN508HES
74 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
227
FDTN-H
Preset point of the protective devices
Parts name Mark
Thermistor
(for protection over-
loading in heating)
Thermistor
(for frost prevention)
Thermistor
(for detecting dis-
charge pipe temp.)
Thermistor
(for detecting heat
exchange temp.)
High pressure switch
(for controlling FM0)
OFF 68˚C
ON 61˚C
Equipped
unit
ThI-R
Tho-D
Tho-R
63H2
Indoor unit
Outdoor unit
Outdoor unit
Outdoor unit
FDTN308~508
(FDC308~508 type only)
FDT308~508
OFF 2.5˚C
ON 10˚C
OFF 135˚C
ON 90˚C
OFF 70˚C
ON 60˚C
OFF 2.5MPa (25.5 Kgf/cm
2
G)
ON 2.06MPa (21 kgf/cm
2
G)
Parts name Mark
Thermistor
(for protection over-
loading in heating)
Thermistor
(for frost prevention)
Defrost thermostat
High pressure switch
(for controlling FMo)
OFF 68˚C
ON 61˚C
Equipped
unit
THI-R
23DH
2
23DH
1
63H2
Indoor unit
Outdoor unit
Outdoor unit
FDTN208~508
(FDC208, 258 or FDC206~506 type only)
FDT208~508
OFF 2.5˚C
ON 10˚C
OFF 12˚C
ON -6˚C
OFF 2.5MPa (25.5 Kgf/cm
2
G)
ON 1.86MPa (19 kgf/cm
2
G)