11-2-1. troubleshooting check table
OPERATION
INDICATOR
lamp
Before taking measures, make sure that the symptom reappears, for accurate troubleshooting.
Self check table
NO.
1
2
3
Abnormal
point
Mis-wiring
Serial sig-
nal
Indoor coil
thermistor
Room
tempera-
ture ther-
mistor
Defrost
thermistor
Indication
0.5-second ON
0.5-second OFF
1-time flash
2.5-second OFF
2-time flash
2.5-second OFF
6-time flash
2.5-second OFF
Symptom
Outdoor unit
does not run.
Outdoor unit
does not run.
Outdoor unit
does not run
Detect method
When serial signal stops for 4
to 5 seconds after 1st on of
52C contactor by POWER
turning on.
When serial signal from out-
door unit stops for 4 to 5 sec-
onds.
Detect Indoor coil/room tem-
perature thermistor short or
open circuit every 8 seconds
during operation.
When the defrost thermistor
shorts or opens after the com-
pressor start-up.
Check point
Check wiring (visual check and conductiv-
ity check).
Check indoor electronic control
P.C.board.
Check outdoor DEICER P.C. board.
Check electrical parts.
Check resistance of thermistor.
Re-connect connector.
Check indoor electronic control P.C.board.
Check outdoor DEICER P.C. board.
Check resistance of thermistor.
Re-connect connector.
4
Outdoor
power
system
5-time flash
2.5-second OFF
Outdoor unit
does not run
When the compressor opera-
tion is continuously three times
interrupted by over current
protection within 1 minute after
start-up , it stops operation.
Check the inverter output.
Check the compressor.
5
Outdoor
control
P.C. board
MCFH-
24NV only
7-time flash
2.5-second OFF
Outdoor unit
does not run
When it cannot properly read
data in the nonvolatile memory
of the outdoor control
P.C.board.
Check the outdoor control P.C.board.
6
Outdoor
refrigerant
system
error
10-time flash
2.5-second OFF
Outdoor unit
does not run
When the compressor opera-
tion has been interrupted by
LEV protection continuously 5
minutes, the compressor stops
operation.
Amount of gas.
Check the outdoor control P.C. board.
Contact of LEV board connectors.
The indication is shown only when the indoor unit connects with the outdoor unit MXZ-32SV- .
E1