• The following indication does not depend on the shape of lamp.
Before taking measures, make sure that the symptom reappears, for accurate troubleshooting.
No.
1
2
4
5
6
SymptomOperation indicator lamp Detection method
Checkpoint
0.5-second ON
0.5-second OFF
1-time flash
2.5-second OFF
Mis-Wiring
Serial sig-
nal
MSH-24RV
Outdoor
thermistor
Outdoor
control
system
Indoor coil
thermistor
3 minutes after power supply turns ON, when
serial signal is not received.
When serial signal from outdoor unit stops for
4 to 5 seconds.
<Thermistor short>
Thermistors are abnormal when they short
after compressor start-up.
<Thermistor open>
Thermistors are abnormal when they open
after compressor start-up.
However, discharge temperature thermistor is
abnormal when open circuit is detected more
than 10 minutes after compressor start-up.
When it cannot properly read data in the
nonvolatile memory of the deicer P.C. board,
outdoor unit stops [and restarts 3 minutes
later(MSH-24RV).]
• Shortage of refrigerant
• Replace the deicer P.C.
board.
Refer to J "Check of outdoor
thermistor" on page 66.
• Replace the deicer P.C.
board.
• Refer to H "How to check
mis-wiring " on page 65.
• Refer to G "How to check
mis-wiring and serial signal
error" on page 64.
3
Indoor fan
motor
7
Low
discharge
temperature
protection
MSH-30RV
When discharge temperature has been 50:
or less on cool operation, or has been 49: or
less on heat operation for 20 minutes.
Abnormal
point
Outdoor unit
does not
operate.
Room
tempera-
ture
thermistor
2-time flash
2.5-second OFF
Detect Indoor coil/room temperature
thermistor short or open circuit every 8
seconds during operation.
• Refer to the characteristics of
main indoor coil thermistor,
sub indoor coil thermistor,
and room temperature
thermistor on page 67 or 68.
3-time flash
2.5-second OFF
Indoor fan
repeats 12
seconds ON
and 3
minutes
OFF.
When the
indoor fan
breaks, the
fan keeps
stopping.
When rotational frequency feedback signal is
not emitting during 12-second indoor fan
operation.
• Refer to A "Check of
indoor fan motor" on page 59.
4-time flash
2.5-second OFF
Indoor
control
system
MSH-30RV
When it cannot properly read data in the
nonvolatile memory of the indoor electronic
control P.C. board.
Outdoor unit
does not
operate.
Outdoor unit
does not
operate.
• Replace the indoor electronic
control P.C. board.
6-time flash
2.5-second OFF
• Refer to I "Check of LEV" on
page 66.
• Check refrigerant circuit and
refrigerant amount.
Outdoor unit
does not
operate.
Outdoor unit
does not
operate.
Outdoor unit
does not
operate.
7-time flash
2.5-second OFF
10-time flash
2.5-second OFF
abnormalities.