134
No.
SW1
setting
Display mode
Display on the LED1, 2 (display data)
Notes
12345678 1 2 3 4 5 6 7 8
195 11000011
IC1 LEV opening pulse
at time of abnormality
0–2000 (pulse)
Display of opening pulse
of indoor LEV at time of
abnormality
196 00100011
IC2 LEV opening pulse
at time of abnormality
197 10100011
IC3 LEV opening pulse
at time of abnormality
198 01100011
IC4 LEV opening pulse
at time of abnormality
199 11100011
IC5 LEV opening pulse
at time of abnormality
200 00010011
High pressure sensor
data at time of
abnormality
−99.9–999.9 (PSIG)
Display of data from High
pressure sensor, and all
thermistors, at time of
abnormality.
201 10010011
TH4 (Compressor)
sensor data at time of
abnormality
−99.9–999.9 (
_
F)
202 01010011
TH6 (Suction pipe)
sensor data at time of
abnormality
203 11010011
TH3 (Outdoor liquid
pipe) sensor data at
time of abnormality
204 00110011
TH8 (Heat sink)
sensor data at time of
abnormality
205 10110011
OC SC (cooling) at time of
abnormality
−99.9–999.9 (degree)
Display of outdoor SC
data at time of abnormality
206 01110011
IC1 SC/SH at time of
abnormality
−99.9–999.9 (degree)
During heating: subcool (SC)
During cooling; superheat (SH) (Fixed to "0" during cooling operation)
Display of indoor SC/SH
data at time of abnormality
207 11110011
IC2 SC/SH at time of
abnormality
208 00001011
IC3 SC/SH at time of
abnormality
209 10001011
IC4 SC/SH at time of
abnormality
210 01001011
IC5 SC/SH at time of
abnormality
211 11001011 IC6 Capacity code
0–255
Display of indoor unit
capacity code
The No.1 unit will start from
the M-NET address with the
lowest number
212 00101011 IC7 Capacity code
213 10101011 IC8 Capacity code
214 01101011
IC6 operation mode
STOP Fan
Cooling
thermo-ON
Cooling
thermo-OFF
Heating
thermo-ON
Heating
thermo-OFF
Display of indoor unit
operation mode
215 11101011
IC7 operation mode
216 00011011
IC8 operation mode
217 10011011
IC6 LEV opening pulse
0–2000 (pulse)
Display of opening pulse of
indoor LEV
218 01011001
IC7 LEV opening pulse
219 11011001
IC8 LEV opening pulse
OCH573C