EasyManua.ls Logo

Mitsubishi MXZ-4C36NAHZ - Page 74

Mitsubishi MXZ-4C36NAHZ
162 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Check code
4210
(UP)
Compressor overcurrent interruption
●Diagnosis of defectives
Make sure to turn the power OFF before connecting/disconnecting any connectors, or replacing boards.
Diagnosis Remedy
Chart 2 of 2
No
Yes
Yes
No
Yes
Yes
No
Yes
No
No
Are they connected properly?
Connect the compressor wiring (U, V and
W phase) properly, then turn the power
back ON.
Continued from the previous page
Does it operate normally?
Are those units short-cycled?
Are the voltage among the phases
U-V, V-W and W-U different?
Does it operate normally?
Check the DC fan motor.
Remove factor(s) causing the short-cycle.
Replace the compressor.
Replace the outdoor power board.
Complete
Check the operation of indoor/outdoor fan
motors.
Check for indoor/outdoor short-cycle.
Disconnect the compressor wiring from the outdoor
power board, then check the voltage among each
phases U, V and W during test run (SW7-1 ON).
Make sure to perform a voltage
check with the same performing
frequencies.
Replace the outdoor controller board.
(short-cycled)
(no short-cycled)
74
OCH573C

Related product manuals