85
OPERATING PROCEDURE
PHOTOS
Photo 12
Reactors
Reactor box
Propeller
12. Removing the reactors (ACL1, ACL2, ACL3)
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
(3) Remove the 6 screws, screw 8 and 9 (5 × 10), that fix
the front panel and remove the front panel. (See photo 3.)
(4) Remove the 2 screws, screw 0 and 1 (both 4 × 10),
that fix the separator, screw 0 from the valve bed and
screw 1 from the bottom of the separator, and tilt the
separator to the side of the fan motor slightly.
(See photo 11.)
(5) Disconnect the lead wires from the reactor and remove the
4 screws, screw 2, that fix the reactor to remove the
reactor. (See photo 12 and 13.)
Note 1: The reactor is very heavy (4kg)! Be careful when
handling it.
Note 2: The reactor box is also removable.
Photo 11
Electrical parts box
Screw0
Valve
bed
Screw1
Separator
Reactor box
Electrical
parts box
4-way valve
Photo 13
Screw2
Reactor box