11
6. Electrical work
6.3. Wiring transmission cables
1 Types of control cables
1. Wiring transmission cables
• Typesoftransmissioncables:ShieldingwireCVVSorCPEVSorMVVS
• Cablediameter:Morethan1.25mm
2
• Maximumwiringlength:Within200m
2. M-NETRemotecontrolcables
Kindofremotecontrolcable Shielding wire (2-core) CVVS, CPEVS or MVVS.
Cable diameter 0.5 to 1.25 mm
2
[AWG 20 to AWG 16]*
Remarks
When 10 m
[32 ft] is exceeded, use cable with
thesamespecicationsastransmissionline
wiring.
* Connected with simple remote controller.
M1
S
M2
BA
C
M1
S
M2
TB3TB1 TB7
D
L1
L2
GR
6.2. Control box and connecting position of wiring
(Fig. 6-1)
1. Connect the branch box transmission line to transmission terminal block (TB3),
or connect the wiring between outdoor units or the wiring with the centralized
control system to the centralized control terminal block (TB7).
When using shielded wiring, connect shield ground of the branch box transmis-
sion line to the screw (C or D) and connect shield ground of the line between
outdoor units and the central control system transmission line to the shield (S)
terminal of the centralized control terminal block (TB7) shield (S) terminal. In
addition,inthecaseofoutdoorunitswhosepowersupplyconnectorCN41has
beenreplacedbyCN40,theshieldterminal(S)ofterminalblock(TB7)ofthe
centralized control system should also be connected to the screw (C or D) using
attached lead wire.
2. Conduit mounting plates are being provided. Pass the power supply and
transmission wires through the appropriate knock-out holes, then remove the
knock-out piece from the bottom of the terminal box and connect the wires.
3. Fix power source wiring to terminal box by using buffer bushing for tensile force
(PG connection or the like).
Caution:
Never connect the transmission line for the branch box or the central control
system transmission line to this terminal bed (TB1B). If the transmission
lines are connected, the indoor unit terminal block, branch box terminal
block or centralized control terminal block could be damaged.
Fig. 6-1
3. MA Remote control cables
Kindofremotecontrolcable Sheathed 2-core cable (unshielded) CVV
Cable diameter 0.3 to 1.25 mm
2
(0.75 to 1.25 mm
2
)*
Remarks Within 200 m
* Connected with simple remote controller.
2 Wiring examples
• Controllername,symbolandallowablenumberofcontrollers.
Name Symbol Allowable number of controllers
Outdoor unit controller OC –
Indoor unit controller IC
PUMY-P36NKMU1 1 to 7 units per 1 OC
PUMY-P48NKMU1 1 to 10 units per 1 OC
Remote controller RC MA Maximum of 2 per group
CONDUITPLATE:
accessory
ø24knock-outhole
(For transmission wires)
ø37knock-outhole
(For power supply wires)
CONDUITWASHER:
accessory
Example of a group operation system with multiple outdoor units (Shielding wires and address setting are neces-
sary.)
<Examples of Transmission Cable Wiring>
■ M-NET Remote Controller (Fig. 6-2)
■ MA Remote Controller (Fig. 6-3)
<Wiring Method and Address Settings>
a. Always use shielded wire when making connections between the outdoor unit (OC) and the indoor unit (IC), as well for all OC-OC, and IC-IC wiring intervals.
b. UsefeedwiringtoconnectterminalsM1andM2andthegroundterminalonthetransmissioncableterminalblock(TB3)ofeachoutdoorunit(OC)toterminalsM1,M2
and terminal S on the transmission cable block of the indoor unit (IC).
c. Connect terminals 1 (M1) and 2 (M2) on the transmission cable terminal block of the indoor unit (IC) that has the most recent address within the same group to the
terminal block on the remote controller (RC).
d. Connect together terminals M1, M2 and terminal S on the terminal block for central control (TB7) for the outdoor unit (OC).
e. ThejumperconnectorCN41onthecontrolpaneldoesnotchange.
f. Connect the terminal S on the terminal block for central control for the power supply unit to the ground terminal (
) in the electrical component box.
g. Set the address setting switch as follows.
Unit Range Setting Method
IC (Main) 01 to 50 Usethemostrecentaddresswithinthesamegroupofindoorunits
IC (Sub) 01 to 50
Useanaddress,otherthanthatoftheIC(Main)fromamongtheunitswithinthesamegroupofindoorunits.Thismustbein
sequence with the IC (Main)
OutdoorUnit 51 to 100
Usethemostrecentaddressofalltheindoorunitsplus50
* The address automatically becomes “100” if it is set as “01 - 50”.
M-NETR/C(Main) 101 to 150 Set at an IC (Main) address within the same group plus 100
M-NETR/C(Sub) 151 to 200 Set at an IC (Main) address within the same group plus 150
MA R/C – Unnecessaryaddresssetting(Necessarymain/subsetting)
h. The group setting operations among the multiple indoor units is done by the remote controller (RC) after the electrical power has been turned on.
<Permissible Lengths>
1 M-NET Remote controller
• Maxlengthviaoutdoorunits:L
1+L2+L3+L4 and L1+L2+L3+L5 and L1+L2+L6+L7 500 m [1640 ft] (1.25 mm
2
[AWG16] or more)
• Maxtransmissioncablelength:L
1 and L3+L4 and L3+L5 and L2+L6 and L7 200 m [656 ft] (1.25 mm
2
[AWG16] or more)
• Remotecontrollercablelength:
ℓ1, ℓ2, ℓ2 +ℓ3, ℓ4 10 m [33 ft] (0.5 to 1.25 mm
2
[AWG20 to AWG16])
If the length exceeds 10 m [33 ft], use a 1.25 mm
2
[AWG16] shielded wire. The length of this section (L8) should be included in the
calculation of the maximum length and overall length.
2 MA Remote controller
• Maxlengthviaoutdoorunit(M-NETcable):L
1+L2+L3+L4 and L1+L2+L6+L7 500 m [1640 ft] (1.25 mm
2
[AWG16] or more)
• Maxtransmissioncablelength(M-NETcable):L
1 and L3+L4 and L2+L6 and L7 200 m [656 ft] (1.25 mm
2
[AWG16]
or more)
• Remotecontrollercablelength:m
1 and m1+m2 +m3 and m1+m2+m3+m4 200 m [656 ft] (0.3 to 1.25 mm
2
[AWG20 to AWG16])
C Screw on the electrical component box
D Screw on the electrical component box
A Power source
B Transmission line
RG79F079H01_EN.indd 11 2/24/2016 2:57:23 PM