Moeller P7 Series - Circuit Breaker Setting and Adjustment; Adjusting Rated Operational Current (Iu); Setting Short-Time Delayed Overcurrent Release (Irm); Adjustment Range Limitations

Moeller P7 Series
10 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5/9
90
80
100
z. B./e. g./par ex./per es./por ej./ :
I
u
= 200 A
I
r
= 180 A
2
rm
r
Einstellung nicht über Höchstmarke drehen
Do not turn dial beyond highest setting
Le réglage ne doit pas dépasser la valeur maximale
Non ruotare oltre il punto massimo di taratura
No gire la esfera más allá del ajuste más alto
Z 2
1
Einstellung
Setting
Réglage
Taratura
Regulación
NZM7(4)-...N(S, H)
1
2
12
6
3
rm
r
z. B./e. g./par ex./per es./por ej./ :
I
u
= 200 A
I
rm
= n x I
u
I
rm
= 6 x 200 A = 1200 A
Einstellung nicht über Höchstmarke drehen
Do not turn dial beyond highest setting
Le réglage ne doit pas dépasser la valeur maximale
Non ruotare oltre il punto massimo di taratura
No gire la esfera más allá del ajuste más alto
10/99 AWA 123-1337