STF-R/C Hardware Manual
 400-820-9661
RS-485 network connection
Multiple –R model drive network can be built via dual RS-485 communication port by network 
cable provided. 
RS-485 Four-wire Configuration
RS-485 four-wire system utilize separate transmit and receive wires. One pair of wires connect 
the host’s transmit signals(TX+/TX-) to each drive’s RX+/RX- receive terminals. The other pair 
connects the drive’s TX+/TX- terminals to the host’s receive signals. A logical ground terminal is 
provided on each drive and can be used to keep all the drives at the same ground potential. The 
rst drive’s logical GND of the RS-485 bus must connect to host’s ground.
Four-wire Connection
Connect the drive’s RX+ to the TX+ terminal of the host controller,and connect the drive’s RX- to 
the TX- terminal of the host controller . Connect the drive’s TX+ to the RX+ terminal of the host 
controller,and connect the drive’s TX- to the RX- terminal of the host controller .
Connect the drive’s GND and the host’s GND to a same ground.
NOTE: The RS-485 port on the drive is isolated from internal circuitry of the drive. So the 
GND of each drive’s RS-485 port must be connected together. The rst drive’s GND of the 
RS-485 port must be connected to the GND of RS-485 port on the host PC or controller.
RS-485 Tow-wire Configuration 
In a two-wire system ,the data transmitting and receiving use a same cable. the host must stop 
its transmitting before receiving data. That means the host must stop transmit data before drive 
begins to answer a query which just come from the host, otherwise the host cannot receive 
any data witch sent from a drive. There is a transmit delay parameter that can be adjusted to 
compensate for a host that is slow to disable its transmitter. This adjustment can be set over the 
network using the TD command,it also can be set by using the STF Congurator software. Users 
can set a shorter transmit delay in a four-wire system. 
Two-wire connection 
The RX+ and TX+ of the drive connect to the host’s + in parallel. The RX- and TX- of the drive 
connect to the host’s - in parallel. Connect the drive’s GND and the host’s GND to a same ground.
NOTE: The RS-485 port on the drive is isolated from internal circuitry of the drive. So the 
GND of each drive’s RS-485 port must be connected together. The rst drive’s GND of the 
RS-485 port must be connected to the GND of RS-485 port on the host PC or controller.