RIY
6
The Interface Solution Experts
Input
1
Code
R0
R1
R2
R3
R4
R5
R6
R7
R8
R9
R10
R11
R12
R13
R14
R15
PRG
SW302
Setting
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
Table 2. RTD and Ohms Input by Input Code (SW302 Settings)
Input
Type
Pt 100Ω
385 RTD
Pt 100Ω
3923 RTD
Pt 100Ω
3916 RTD
Pt 100Ω
3902 RTD
Pt 200Ω
385 RTD
Pt 500Ω
385 RTD
Pt 1000Ω
385 RTD
Pt 1000Ω
375 RTD
Two Pt 100Ω
385 RTD’s, Ave.
Two Pt 100Ω
3923 RTD’s, Diff.
Two Pt 100Ω
385 RTD’s, Diff.
Two Pt 500Ω
385 RTD’s, Diff.
NI 120Ω
RTD
CU 10Ω
RTD
Ohms
FLEX-SOR
TM
Accuracy Adjustments
±0.05% of Span, ±
0.20 °C
(0.36 °F)
0.20 °C
(0.36 °F)
0.20 °C
(0.36 °F)
0.20 °C
(0.36 °F)
0.13 °C
(0.23 °F)
0.10 °C
(0.18 °F)
0.10 °C
(0.18 °F)
0.10 °C
(0.18 °F)
0.20 °C
(0.36 °F)
0.40 °C
(0.72 °F)
0.40 °C
(0.72 °F)
0.20 °C
(0.36 °F)
0.14 °C
(0.25 °F)
1.6 °C
(2.9 °F)
0.2Ω
0.08 °C
(0.14 °F)
Description
100Ω at 0 °C,
α = 0.003850
98.129Ω at 0 °C,
α = 0.003923
100Ω at 0 °C,
α = 0.003916
100Ω at 0 °C,
α = 0.003902
200Ω at 0 °C,
α = 0.003850
500Ω at 0 °C,
α = 0.003850
1000Ω at 0 °C,
α = 0.003850
1000Ω at 0 °C,
α = 0.003750
2 or 3 of R0
Averaged
2 of R1
Differential
2 of R0
Differential
2 of R5
Differential
120Ω at 0 °C,
α = 0.00672
9.035Ω at 0 °C,
α = 0.00427
0-4000Ω
1000Ω at 0 °C,
α = 0.00285
Range
2,3
–200 to 850 °C
(–328 to 1562 °F)
–200 to 600 °C
(–328 to 1112 °F)
–200 to 510 °C
(–328 to 950 °F)
–200 to 650 °C
(–328 to 1202 °F)
–200 to 630 °C
(–328 to 1166 °F)
–200 to 630 °C
(–328 to 1166 °F)
–200 to 630 °C
(–328 to 1166 °F)
–185 to 540 °C
(–301 to 1004 °F)
–200 to 850 °C
(–328 to 1562 °F)
–550 to 800 °C
(–990 to 1440 °F)
–550 to 1050 °C
(–990 to 1890 °F)
–550 to 830 °C
(–990 to 1494 °F)
–80 to 320 °C
(–112 to 608 °F)
–50 to 250 °C
(–58 to 482 °F)
0-4000Ω
–90 to 175 °C
(–130 to 347 °F)
NOTES: 1. This column contains the Input Code for the model number of each RIY.
2. The lower table limit extends 5%, or more, of maximum span below the listed value. When this limit is
exceeded, the RIY will clamp at the limit value and the display will read “–LO–”. For ohms ranges, 0Ω is
the lower table limit.
3. The upper table limit extends 10%, or more, of maximum span above the listed value. When this limit is
exceeded, the RIY will clamp at the limit value and the display will read “–HI–”. For ohms range, 4095Ω
is the upper table limit.
Programmable input, unspecified at time of order; factory default of R0, -300 to +267 °F (see model number).