Failures and Fault Finding:
The different type of failures the boiler will show with a lockout light:
F01
The boiler trys 3 times to establish the ame:
each sequence lasts 6 seconds between
each sequence the stop time is 5 seconds
If the ionisation electrode fails to detect a flame
the boiler will lock out (F1)
locked.
When the boiler is working and the ame fails due to a malfunction of the gas valve
or ionisation electrode after 1 second without ame detection the boiler will shut down
(gas valves) The boiler will then attempt to relight if no flame is detected the boiler will
lock out (F1)
lapoouuuuuuuuuuuuuuuuuuuuufdfd
no oiuuuuuuuuuuuuuuAC ppppp
POSSIBLE CAUSES
-NO GAS
-NO SPARK
- FAULTY GAS VALVE
- FAULTY IONISATION ELECTRODE
- FAULTY PCB