Troubleshooting 28
7.8 PC 08 (Overload current protection diagnosis and solution)
Description: An abnormal current rise is detected by checking the specified current detection circuit.
Recommended parts to prepare:
Outdoor PCB
Connection wires
Compressor
Troubleshooting and repair:
Check the power supply.
Do any exist?
Are they within acceptable
parameters?
Are they properly connected ?
Is it in working order?
Replace the outdoor unit.
Is it in working order?
Check system for blockages.
YES
Stop the unit.NO
Clear the blockage.
Yes
Check the compressor resistance values.
No
Replace the compressor.NO
Check the connections and wires.
YES
Ensure proper connections or
replace the wires.
NO
Check the reactor.
YES
YES
Replace outdoor PCB.NO
Note: For certain models, outdoor PCB could not be removed separately. In this case, the outdoor electric
control box should be replaced as a whole.