Unit Installation
Fig. 2.6
Fig. 2.7
Install an oil
return bend
every 19.7 ft
(6 m)
Oil return bend
System gas pipe
Outdoor unit
Indoor unit
Outdoor unit
Non-return bend
System gas pipe
Oil return bend
Indoor unit
Install an oil
return bend
every 19.7 ft
(6 m)
OIL RETURN BENDS
Add an oil return bend as described below:
If outdoor unit is beneath the indoor unit, there is no need to add a non-return bend at the
lowest or highest position of the vertical pipe, as shown below in Fig. 2.6:
If outdoor unit is above the indoor unit, it is necessary to add an oil return bend and a
non-return bend at the lowest and highest position of the vertical pipe, as shown below in Fig. 2.7:
Use the following dimensions in Fig. 2.8 to form the oil return bend(s):
C
B
A
A (Pipe Diameter)
B C
Ф12
Ф1/2
≥26
≤150
Ф16
Ф5/8
≥33 ≤150
Ф19
Ф3/4
≥34
≥1
≥1.3
≥1.34
≥5.91
≥5.91
≥5.91
≤150
Fig. 2.8
mmInches mmInches mmInches
For installation with a No-Vac® Quick Connect® Line Set, refer to the next section starting on page 24