CHILLERS
MAINTENANCE AND OPERATING MANUAL
38178800511
Original instructions
TAEevo M05-M10

Questions and Answers

  • S
    Samuel CruzAug 14, 2025
    Why is the MTA TAEevo M10 Chiller water temperature too high?
    • P
      paulwilsonAug 14, 2025
      The water temperature in your MTA Chiller might be higher than expected due to several reasons: the thermal load could be too high (restore it to the preset limits), the ambient temperature could be too high (restore it to the preset limits), the condenser fins may be dirty (clean them), the front surface of the condenser could be obstructed (free it), or there might not be enough refrigerant fluid in the plant (in this case, get a technician to check for and eliminate leaks, then refill the plant).
  • P
    Peter AnthonyAug 21, 2025
    What causes the compressor protection to trip on my MTA Chiller?
    • A
      Antonio BakerAug 21, 2025
      The compressor protection on your MTA Chiller might trip due to: a thermal load that is too high in conjunction with a high ambient temperature (stop the machine and restore the load within the preset limits, then wait a few minutes before restarting), a thermal load that is too high along with a lack of refrigerant in the circuit (get a technician to check for and eliminate leaks, then have the engineer refill the circuit), or the same issues that cause the high pressure switch to trip.
  • T
    Tracy HensonAug 25, 2025
    What to do if my MTA TAEevo M10 is obstructed and the water isn't flowing?
    • J
      Jaime KlineAug 25, 2025
      If your MTA Chiller is obstructed and the water isn't flowing, it could be because the set point is too low, causing the water to freeze (raise the set point or add an appropriate percentage of ethylene glycol (antifreeze)), or the evaporator is obstructed by dirt carried by the water to be cooled (clean the evaporator by running a detergent solution which is not aggressive for steel, aluminium and copper, or run a high water flow against the stream and install a filter upstream from the chiller).
  • H
    haley45Aug 27, 2025
    Why does the FC1 fuse trip on my MTA TAEevo M10 Chiller?
    • J
      Joanna StewartAug 27, 2025
      The FC1 fuse in your MTA Chiller might be tripping because of compressor motor overloading or a short circuit, or a short circuit in the compressor power line. To resolve this, use a tester to check the motor windings and the power cable. Replace the compressor or cable if necessary, and then change the fuse.
  • R
    Robert JonesAug 31, 2025
    Why is the FF1 fuse tripping in my MTA Chiller?
    • A
      annette53Aug 31, 2025
      The FF1 fuse in your MTA Chiller may be tripping due to fan, pumps, and electronic power overload, or a short circuit in the power line. Check the components and wiring with a tester, replace any damaged components or wiring, and then change the fuse.
  • H
    hughesjaredSep 3, 2025
    Why is the water pressure low at the pump outlet of my MTA TAEevo M10?
    • D
      Destiny ParkerSep 3, 2025
      Low water pressure at the pump outlet of your MTA Chiller could be due to excessive clearance between the impeller and the pump casing, indicating worn parts. You should verify and replace the pump impeller.
  • P
    Patrick LynnSep 6, 2025
    How to fix a faulty -BT1 probe on my MTA Chiller?
    • J
      John MolinaSep 7, 2025
      A faulty -BT1 probe on your MTA Chiller, or parameters out of range, can be resolved by checking or renewing the probe.
  • B
    brandongraySep 10, 2025
    What to do if MTA TAEevo M10 continues to operate with old values after parameter modification?
    • X
      xhooverSep 10, 2025
      If your MTA Chiller continues to operate with the old values after modifying a parameter, it may be because the instrument has not updated the old value or the parameter programming procedure was not concluded correctly. Turn the instrument off and on again or re-program the parameters correctly.
  • D
    Darlene RiceNov 16, 2025
    What to do if the high pressure switch (HP) trips on my MTA TAEevo M10?
    • S
      Sydney OwensNov 16, 2025
      If the high pressure switch (HP) trips on your MTA Chiller, it could be due to several reasons: the fan may not be working (repair or replace it, and check the thermal protection switch if fitted, then press the reset button on the cap of the pressure switch), the ambient air temperature may be too high (reduce ambient temperature within design limits by increasing local ventilation, then press the reset button on the cap of the pressure switch), there could be recirculation of warm air due to incorrect installation location (change the position of the unit or any adjacent obstructions to avoid recirculation, then press the reset button on the cap of the pressure switch), the condenser fins may be dirty (clean the condenser fins, then press the reset button on the cap of the pressure switc...

Summary

SAFETY

General Safety Instructions

Covers general safety precautions for personnel operating and maintaining the unit.

Precautions for Liquids and Handling

Specific safety guidelines for handling cooling liquids and general unit handling.

Refrigerant Safety and First Aid

Details safety measures for refrigerant gas R407C, including dangers and first aid.

INSTALLATION

START UP

Initial Start Up Procedure

Step-by-step guide for the initial startup of the chiller unit.

OPERATION AND MAINTENANCE

Unit Operation and Maintenance Access

Explains normal operation and how to access unit components for maintenance.

TROUBLE SHOOTING

Comprehensive Troubleshooting Guide

A detailed guide listing problems, their causes, symptoms, and recommended remedies.

Troubleshooting Guide (Continued)

Continuation of the detailed troubleshooting guide for various unit issues.

MTA TAEevo M10 Specifications

General IconGeneral
BrandMTA
ModelTAEevo M10
CategoryChiller
LanguageEnglish