TAEevo M05-M10
14
The data inside this manual are not binding and they can be modified by the manufacturer without notice. All rights reserved.
7.8.2 Display
7.8.3 Defrost parameters (function not active)
OdS
Power on outputs
activation delay
At the time of power-on activation of all loads is inhibited for
the time set
0255min0
AC
Anti-hunting
delay
Minimum interval between compressor stop and successive
start
050min6
CCt
Continuous cycle
duration
To set the continuous cycle duration, to be used for example
when filling the cold store with new products.
024 h°C0
CCS
Continuous cycle
set-point
This set-point is used during the continuous cycle -50 150 °C -5
COn
Compressor On
time with faulty
probe
Time for which the compressor continues to run in the
presence of a probe fault
COn=0 the compressor always remains stopped (*)
(*) If COn=0 and “COF”=0 the compressor is stopped
0255min0
COF
Compressor Off
time with faulty
probe
Time for which the compressor remains stopped in the
presence of a probe fault
COF=0 the compressor is always on
0255°C0
Parameter Description Min. Max. U.M.
Factory
settings
CF
Temperature unit
of measurement
Serves to set the unit of measurement.
If the unit of measurement is changed the following
parameters must be reset: Hy, LS,US, Ot, ALU, ALL
°C÷°F °C
rES
Resolution Allows the decimal point to be displayed
in=1°C
dE=0,1°C
dE
Lod Display
Select the probe to be displayed
P1= thermostat probe
P2= evaporator probe
P3= probe (P3 not active)
P4= probe (P4 not active)
Set= set-point
dtr= display percentage
P1
dLy
Temperature
display time lag
As the temperature rises the displayed value increases by 1
degree Celsius or Fahrenheit every dLy minutes.
020.0min0
Parameter Description Min. Max. U.M.
Factory
settings
tdF
Type of
defrosting
Serves to choose the type of defrosting
El= heater
in= hot gas
El
dtE
Defrost End
Temperature
Establishes the evaporator temperature that determines the end
of the defrost cycle.
-50 50 °C 8
ldF
Defrost cycles
interval
Establishes the interval between the start of two defrost cycles
0120h 6
MdF
Defrost duration Establishes maximum defrost duration
P2P= n no evaporator probe (time controlled
defrosting) establishes the defrost duration
time
P2P= y (defrost end at temperature) becomes
the maximum defrost duration
(*) 0 inhibit defrost cycle
0255min0
dSd
Defrost start
delay
Serves to diversify defrost starts avoiding system overloads
059min0
Parameter Description Min. Max. U.M.
Factory
settings
Table 4 C
ONTROL
PARAMETERS