Password = 19 » Power On Time & ITD Time Selection
» Under Current, Over Current,
Under Voltage, Over Voltage,
Under Frequency, Over Frequency
Password = 29 » Single Phase Prevention (SPP)
Short Circuit, Lock Rotor Point,
Unbalance Current, Phase Sequence,
Phase Loss
Password = 39 » Network Selection & CT Ratio Selection
Password = 59 » Display Mode Selection (Hold / Scroll)
Press & Key Together Reset mode , Initial Trigger,
Relay Fault mode selection.
»
Long Press Key
SET
Long Press Key to enter into Password
SET
PARAMETER SETTING
Press Key
SET
Enter Password = 19
Power on
Time
(0-99 Sec)
p O N
T I M
5
Initial Delay
Time
(0-99 sec)
Under Current
If Enable
(Enable/Disable)
Under Current
Value
(0.00-CTR)
Under Current
Delay Time
(0-999 Sec)
Over Current
(Enable/Disable)
Over Current
Value
(0.00-CTR)
Over Current
Trip on
( Time/Curve )
Over Current
Curve Value
(2.5C/5.0C/
10C )
P A S
1 9
I T D
T I M
5
U N C
E N B
U N C
V A L
2 0 0
U N C
T I M
5
O V C
E N B
O V C
V A L
5 0 0
O V C
T R P
T I M
O V C
T I M
5
Over Current
Delay Time
(0-999 Sec)
O V C
C R V
5 0 C
Curve
If
Time
If
Over Voltage
(Enable/Disable)
O V V
E N B
If
Disable
If Enable
If Disable
Press Key
SET
Press Key
SET
Press Key
SET
Press Key
SET
Press Key
SET
Press Key
SET
Press Key
SET
Press Key
SET
Press Key
SET
Over Voltage
Value
(50-550V for 3Ø3W)
(30-330V for 3Ø4W)
O V V
4 8 0
v A L
O V V
5
t I M
(0-999 sec)
Over Voltage
Delay Time
U N V
E N B
Under Voltage
(Enable/Disable)
U N V
V A L
3 8 0
Under Voltage
Value
(50-520V for 3Ø3W)
(30-300V for 3Ø4W)
U N V
T I M
5
Under Voltage
Delay Time
(0-999 Sec)
U F
E N B
Under Frequency
Enable / Disable
U F
4 5 0
V A L
U F
5
T I M
Under Frequency
(45.0 to 65.0Hz)
Value
Under Frequency
(0 to 999 sec)
Delay time
O F
E N B
Over Frequency
(Enable / Disable)
O F
5 5 0
V A L
Over Frequency
(45.0 to 65.0Hz)
Value
O f
5
T I M
Over Frequency
(0 to 999 sec)
Value
If Enable
If
Disable
If
Disable
If
Disable
If Enable
Press Key
SET
Press Key
SET
Press Key
SET
Press Key
SET
Press Key
SET
Press Key
SET
Press Key
SET
Press Key
SET
Press Key
SET
Press Key
SET
Press Key
SET
Press Key
SET
Press Key to Save & exit
SET
If
Disable
If Enable
If Enable
Page - 5

Other manuals for MULTISPAN MPD-152

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the MULTISPAN MPD-152 and is the answer not in the manual?

MULTISPAN MPD-152 Specifications

General IconGeneral
BrandMULTISPAN
ModelMPD-152
CategoryProtection Device
LanguageEnglish

Related product manuals