Page 1
UTC-4201A
OUTPUT SPECIFICATION
AUXILIARY SUPPLY:
TEMPERATURE CONTROLLER
Relay
Supply voltage
Relay Type
Power consumption
(VA RATING)
Rating
1 nos.
1 C/O (NO-C-NC)
Approx 4 VA @ 230V AC MAX
5A, 230V AC/30 V DC
ENVIRONMENT CONDITION:
Relative Humidity
Protection Level
Operating Temp.
0°C to 55°C
UP to 95% RH
(non-condensing)
IP-65 (Front side) As per IS/IEC
60529 : 2001
100 to 270V AC, 50-60Hz
Input Types
Resolution
Indication
Accuracy
Input Range
0 to 600°C,
0 to 1200°C,
-99 to 400°C,
-99.9 to 400.0°C,
J
K
PT-100
PT.1
J,K,PT-100 = 1°C
±1% of FSD ± 1°C
PT.1 = 0.1°C
Display
Heating
Size
Keys
Cooling
Panel Cutout
Upper: 4 digit, 7 segment, 0.56” Red
1) PID control with Auto-Tuning
1) BL.TP (Blower Time Proportion)
Lower: 4 digit, 7 segment, 0.33” Green
2) ON-OFF control
2) ON-OFF control
48 (H) x 48 (W) x 95 (D) mm
SET, INC, DEC, ENT
45 (H) x 45 (W) mm
TECHNICAL SPECIFICATION
(FSD:- full scale deflection)
CONTROL METHOD:
INPUT SPECIFICATION:
DISPLAY AND KEYS:
DIMENSION:
CONTROL METHOD:
Relay Output
48
95
45
45
3
MECHANICAL INSTALLATION
TERMINAL CONNECTION
48
Outline Dimension (mm)
Panel Cutout
Dimension (mm)
PV = Process value
SV = Set Value
Alarm
Inband, Absolute Outband, High,
Absolute Low
Analog Output
0 TO 10V DC
T/C
+
+
RTD
-
-
NC
C
R1
NO
O/P
0TO10V
DC
!
100
270VAC
1
2
3
4
5
L
N
6
7
8
9
10
~
50/60HZ
4VA
Made in India
www.multispanindia.com
O/P
R
TUNE
SET
ENT
UTC 4201A
SV
PV