Modular Water-Cooled
Chillers
Installation, Operation,
Maintenance
MS010XC, MS015XC, MS020XC, MS030XC,
MS040XC, MS050XC, MS070XC, MS085XC
Standard and Total Access™ Modules

Questions and Answers

  • A
    Austin SweeneyAug 19, 2025
    What to do if my Multistack MS070XC Chiller has high discharge pressure (HP)?
    • K
      Kelsey FrankAug 19, 2025
      If your Multistack chiller is showing high discharge pressure, you should check the strainers in the condenser headers and verify the condenser water flow.
  • A
    adam72Aug 21, 2025
    What to do if the Multistack MS070XC Chiller is 'Waiting For Chilled Water Flow'?
    • T
      Timothy BlevinsAug 21, 2025
      If your Multistack chiller displays a 'Waiting For Chilled Water Flow' message, you should: * Check the chilled water pump. * Check the flow switch operation. * Inspect the filter strainers. * Check TB11 inputs #3 - #7.
  • T
    Theresa LewisAug 23, 2025
    What to do if my Multistack MS070XC has low suction pressure (LP)?
    • J
      joshua65Aug 23, 2025
      If your Multistack chiller indicates a low suction pressure, examine the refrigerant charge for leaks and inspect the expansion valve.
  • J
    Jason CohenAug 26, 2025
    What to do if my Multistack MS070XC displays 'Waiting For Condenser Water Flow'?
    • Z
      Zachary LuceroAug 26, 2025
      If your Multistack chiller is displaying 'Waiting For Condenser Water Flow', verify the condenser water pump, check the flow switch operation, inspect the filter strainers, and check TB11 inputs #3 - #8.
  • J
    Jennifer VargasAug 28, 2025
    Why is my Multistack MS070XC at 100% demand all the time?
    • J
      juliearellanoAug 28, 2025
      If your Multistack chiller is constantly at 100% demand, check the entering chilled water sensor and verify the set-points in the system variables.
  • P
    patriciabrewerAug 30, 2025
    Why is my Multistack Chiller experiencing excessive cycling?
    • F
      Frederick ChangAug 30, 2025
      If your Multistack chiller is cycling excessively, check the VSP setting in the system variables, verify the entering CHW sensor location, and look for system problems such as low water volume or low load.
  • P
    perezclaytonSep 1, 2025
    How to troubleshoot a 'Circuit Fault' on a Multistack MS070XC?
    • A
      Autumn RhodesSep 1, 2025
      To troubleshoot a circuit fault on your Multistack chiller, check the components in the control circuit, inspect the wire crimps in the control circuit, and verify the ratio of HP to LP.
  • C
    carolnealSep 4, 2025
    What to do if my Multistack Chiller has low chilled water temperature?
    • L
      Laura RobertsSep 4, 2025
      If your Multistack chiller has a low chilled water temperature, check the LCHW sensor, verify the set-points in the system variables, and check for any flow restrictions.
  • T
    Timothy TannerSep 6, 2025
    What to do if my Multistack MS070XC Chiller shows 'No Demand'?
    • A
      Allison KiddSep 6, 2025
      If your Multistack chiller indicates 'No Demand', check the entering CHW sensor, verify the set-points in the system variables, and check the sensor location.
  • K
    Kimberly JacobsSep 8, 2025
    What to do if my Multistack MS070XC has low suction temperature?
    • D
      Derek JacksonSep 9, 2025
      If your Multistack chiller reports a low suction temperature, check the suction sensor, verify the set-points in system variables, and check for flow restrictions.

Summary

Safety Information

Chiller Components

Master Control Panel

Details the master control panel and its functions.

Compressors, Sensors, and Switches

Describes compressors, sensors, and switches used in the modules.

Standard Modules (Constant Flow Design)

Variable Flow Design for Chilled and Hot Water Standard Modules with Extended Headers on Evaporators and Condensers

Variable Flow Design for Hot Water, Constant Flow for Chilled Water Standard Modules with Extended Headers on Condensers

Variable Flow Design for Chilled Water, Constant Flow for Condenser Water Standard Modules with Extended Headers on Evaporators

Total Access Modules With or Without Variable Flow

Recommended Piping

Pressure Relief Piping and Refrigerant Monitoring

Module Assembly

Module Assembly - Total Access Modules

Multiflush System Assembly

Electrical Installation

Typical Interconnecting Wiring

System Wire & Fuse Sizing Specifications

Installation Checklist & Request for Authorized Start-Up Engineer

Start-Up Data Log

Operation

Sequence of Operation, Leaving Chilled Water Temperature Control

Details the sequence of operation for leaving chilled water temp control.

Factory Setup and Commissioning

Maintenance

Preventive Maintenance Procedures

Guidelines for preventative maintenance tasks.

Strainer Cleaning and Heat Exchanger Cleaning

Annual Maintenance

Troubleshooting