MultiSmart Integrator Guide
Page 12 of 20 MultiSmart_Integrator_Guide_R01.doc
Note 5:
Faults.Well._1.GroupManualReset – resets the following unacknowledged faults :
• HighHighLevel
• HighLevel
• LowLevel
• LowLowLevel
• PrimaryLevelHighRange
• PrimaryLevelLowRange
• PrimaryLevelInvalid
• PrimaryLevelAinOverRange
• PrimaryLevelAinUnderRange
• BackupLevelInvalid
• BackupLevelAinOverRange
• BackupLevelAinUnderRange
• Well 1 PulseStart
• Well 1 PulseStop
Note 6:
Faults.Station.GroupManualReset – resets the following unacknowledged station faults:
• UnderVoltage
• OverVoltage
• VoltsPhaseImbalance
• VoltsPhaseRotation
• DCUnderVoltage
• DCOverVoltage
• MaxOnTime
• MaxOffTime
• PowerFail
• Overflow
• PulseStart
• PulseStop
Note 7:
“Manual mode” on the MultiSmart main display is really “Semi-Auto” mode – which means that the pump will run in manual operation until the cut-out or deactivation point is reached, at which
point the pump mode will revert to “Auto”.
A pump can be placed in true manual mode only by holding the button down on the faceplate. Then, the Manual indication will flash on the LCD and the pump will be forced to run regardless of
the level of the well as long as the button is held down.
A pump can be decommissioned via Settings – Commision/ Decom screen.
Lobley St SPS SP331 General (Electrical Manual (MPA) Multismart Manual Multitrode System Integrator Guide) General
Q-Pulse Id VM357
Active 26/09/2013
Page 12 of 20