25
ON
DP
1 2 3 4
The purpose of code-dial switch
SW1
State :0000
SW2
State:0110
ON
DP
1 2 3 4
SW1
Digits
State
1
2 3
4
ON:1
single phase
Reserved
OFF:0
three phase
SW2
Digits
State
1
2
3
4
ON:1
New transformer
During the modular centralized control, the selection of address code of the unit
OFF:0
Old transformer
The address setting of the last four digits of dial code switch.
Address Code
Unit Number
000
NO.1
001
NO.2
010
NO.3
011
NO.4
100
NO.5
101
NO.6
110
NO.7
111
NO.8
Notice:
Please set NO.1 as master unit and the others as slave units.
There should not be modular units with the same address code, or the units with
the same address code could not start separately, and the status parameters shown on
the centralized wired controller are inaccurate.