Screw Compressor
Instruction Manual
CAUTION
Read this manual carefully and thoroughly before operating, maintaining or inspecting this
product. It is important to fully comprehend the contents of this manual. Keep the operation
manual in a safe, designated place for future reference whenever the need arises.
Specifications of this product are subject to change without prior notice.
125SUD/125LUD
160SUD/160MUD/160LUD
200SUD/200MUD/200LUD
250SUD/250MUD/250LUD
320SUD/320MUD/320LUD/320LLUD
400SUD/400MUD/400LUD/400LLUD/
400XLUD

Table of Contents

Questions and Answers

  • J
    Jessica WrightAug 9, 2025
    Why does my mycom Air Compressor stop immediately after startup?
    • J
      Jonathan ConnerAug 10, 2025
      Your mycom Air Compressor might stop immediately after startup due to a few reasons. It could be that the low pressure protection circuit has been activated, indicating insufficient refrigerant. In this case, check the system, stop any leaks, and recharge the refrigerant, being cautious about moisture contamination. Another cause could be a malfunction in the pressure regulating valve operation, requiring you to replace the valve or remove the cause. Also, consider the possibility of a malfunction in the low pressure protection device, pressure sensor, or relays, where you'll need to identify the malfunctioning devices, examine their causes, take measures, and then replace them. Lastly, motor overload could be the issue; refer to the motor instruction manual for guidance.
  • D
    Derek WilsonAug 14, 2025
    What causes abnormal vibration and/or noise in my mycom Air Compressor?
    • J
      John YatesAug 14, 2025
      Abnormal vibration or noise in your mycom Air Compressor can stem from several issues. Check for insufficient alignment between the compressor shaft and motor shaft, and realign the shaft-center if needed. Another cause could be a large axial runout of the male rotor; if loose locknuts are found and no other fault exists in parts like the thrust bearing, tighten the locknuts evenly. Also, inspect for a loose thrust bearing and replace it if defective. Finally, consider imprecision in the dynamic balance of the rotors, which would require overhauling and inspecting the compressor where rotor dynamic balance measurement and adjustment is feasible.
  • G
    Gregory WagnerAug 31, 2025
    What causes capacity control malfunction in my mycom 320SUD Air Compressor?
    • C
      Cody BoothAug 31, 2025
      Capacity control malfunction in your mycom Air Compressor can be attributed to a few potential causes. It could be due to undetected 100% or 0% by the indicator, in which case you should replace the micro-switch. Another cause may be a malfunction of the unloader solenoid valves or related relays for capacity control; for aging degradation, replace the parts. Internal leakage of the unloader solenoid valves for capacity control can also lead to malfunction; if caused by prolonged low load operation, improve by re-examining the operation method.
  • C
    Cindy HinesNov 4, 2025
    What to do if my mycom 320SUD Air Compressor does not start up?
    • A
      Audrey BrownNov 5, 2025
      If your mycom Air Compressor doesn't start, several factors could be at play. It could be due to the power source being off, so ensure to check the check sheet after inspection to prevent oversight. Other potential causes include a main motor malfunction (refer to the motor instruction manual), undetected capacity control of 0% by the unloader indicator (replace the micro-switch), a capacity control hydraulic circuit defect (readjust), leaks or clogging in pipes and solenoid valves (remove factors and check oil contamination, replacing oil if needed), unconfirmed hydraulic pressure or cooling water circulation (identify malfunctioning devices, examine causes, take measures, and replace devices), clogging in connecting pipes (remove clogging and check oil contamination, replacing oil if nee...
  • D
    Deanna MooreNov 17, 2025
    What to do if there is abnormal high pressure (abnormal discharge pressure) in my mycom 320SUD?
    • K
      kristy80Nov 17, 2025
      If your mycom Air Compressor is experiencing abnormal high pressure, it could be due to several reasons: heat exchange failure at the condenser (clean and wash them, using solvent depending on contamination), malfunction of fan motor, thermo-switch, water spray bars, cooling water pumps, etc. (identify malfunctioning devices, examine their causes, take measures, and replace them), flow volume adjustment failure of cooling water, brine, etc. (readjust manually adjusted regulating valves or examine and address the cause if using an automatic control valve), other causes of insufficient circulation volume of cooling water, etc. (inspect for clogging and contamination of filters for circulation route filters, and take measures as needed), shortage in the capacity of the heat exchanger (re-exam...
  • M
    Melissa HernandezNov 21, 2025
    Why is there low oil-supply pressure in my mycom Air Compressor?
    • R
      rhallNov 21, 2025
      Low oil-supply pressure in your mycom Air Compressor may be attributed to a few potential issues. It could be due to clogging in the oil filter element, indicated by a big difference in outlet/inlet pressures; in this case, remove the clogging, check the oil contamination level, and change the lubricant as necessary. Another cause might be a defect inside the compressor; check the oil contamination level and, after a vibration noise diagnosis, overhaul the compressor if needed. Insufficient oil amount in the oil separator could also be the culprit; inspect the oil heater, relays, and related circuits, and replace parts as needed. Additionally, consider insufficient oil return caused by insufficient refrigerant circulation (resolve the insufficient volume of refrigerant circulation, and the...
  • A
    Alan HowardNov 26, 2025
    What causes a faulty indication of capacity control position in mycom 320SUD Air Compressor?
    • K
      khansenNov 26, 2025
      A faulty indication of capacity control position in your mycom Air Compressor could arise from several factors. It may be due to imprecision in the compressor indicator (manually tighten screws to the 0% indication position of compressor capacity control), imprecision in the controller capacity control indicator (replace the indicator cam), a worn guide pin (dowel pin) of the compressor push rod (replace the dowel pin), malfunction in the potentiometer (replace the potentiometer if caused by aging degradation or prolonged partial load operation), maladjustment of zero point and span adjustment for the E/E positioner (readjust it), malfunction of the E/E positioner or its indicator (replace the E/E positioner for aging degradation), or loose terminals or faulty wiring (tighten loose termina...

Summary

Chapter 1 Safety

Chapter 2 Compressor Specifications and Structure

Chapter 3 Installation

Chapter 4 Compressor and Package Unit Operation

Chapter 5 Maintenance and Inspection

5.1 Precautions for Maintenance and Inspection

Essential safety measures and general precautions to be observed before and during maintenance tasks.

5.2 Maintenance and Inspection Schedule

Details on daily checks, periodic inspections, and overhaul frequency guidelines.

5.3 Compressor Disassembly Preparation and Procedures

Steps and tools required for preparing and executing the compressor disassembly process.

5.4 Disassembly and Inspection of Components

Detailed instructions for disassembling and inspecting individual compressor parts and assemblies.

5.5 Reassembly Procedures

Step-by-step guide for reassembling the compressor components after inspection and repair.

Chapter 6 Troubleshooting

01 Compressor does not start up

Diagnosing and resolving issues when the compressor fails to start.

02 Compressor stops immediately after startup

Troubleshooting steps for compressors that shut down shortly after starting.

04 Low oil-supply pressure

Addressing problems related to insufficient oil supply pressure.

05 Abnormal high pressure (abnormal discharge pressure)

Diagnosing and fixing issues causing abnormally high discharge pressure.

06 Abnormally high discharge temperature

Troubleshooting causes for excessively high discharge temperatures.

07 Leak from mechanical seal

Identifying and rectifying leaks originating from the mechanical seal.

10 Capacity control malfunction

Troubleshooting issues related to the malfunction of the capacity control system.

11 Abnormal vibration and;or noise of compressor

Diagnosing and resolving abnormal vibration and noise issues in the compressor.

mycom 320SUD Specifications