2205B0JE-DA-J-N_2014.05.
3–14–15 Botan Koto-ku, Tokyo 135-8482, Japan
Screw Compressor
J-Series Instruction Manual
170JS-V/170JM-V/170JL-V
220JS-V/220JM-V/220JL-V
280JS-V/280JM-V/280JL-V
CAUTION
Before operating, maintaining, or inspecting this product, read the manual thoroughly and fully
understand the contents.
Keep the operation manual in a safe, designated place for future reference whenever the need
arises.
Specifications of this product are subject to change without prior notice.

Table of Contents

Other manuals for mycom 220JS-V

Questions and Answers

  • S
    Sierra SmithAug 16, 2025
    What causes abnormally high pressure in my mycom Air Compressor?
    • A
      Aaron LewisAug 16, 2025
      Abnormally high pressure in your mycom Air Compressor can be caused by a heat exchange failure at the condenser (heat exchanger). Clean and wash the heat exchangers, using solvent depending on the contamination. Other causes include malfunction of the fan motor, thermo-switch, water spray bars, cooling water pumps, etc. (identify malfunctioning devices, examine their causes, take measures, and replace malfunctioning devices), a flow volume adjustment fault for cooling water, brine, etc. (readjust manually or examine the cause and take measures if an automatic control valve is used), or poor performance in the heat exchanger (re-examine the conditions to improve if the trouble is caused by a change in operating conditions).
  • S
    Shannon SawyerAug 19, 2025
    What to do if my mycom Air Compressor stops immediately after startup?
    • T
      Tyler ArcherSep 12, 2025
      If your mycom Air Compressor stops immediately after startup, it could be due to the low pressure protection circuit being activated. Check for and stop any refrigerant leaks, then replenish the refrigerant, being aware of potential moisture contamination in the system. Another cause might be insufficient refrigerant circulation volume; if there are any heat exchange failures, such as poor defrost performance, investigate the cause and take corrective actions. A malfunction of the low pressure protection device, pressure sensor, relays, etc., could also be the reason. In this case, identify the malfunctioning devices, examine their causes, take appropriate measures, and then replace the faulty devices.
  • J
    Julie HillAug 30, 2025
    What causes faulty indication of capacity control position in my mycom 220JS-V?
    • L
      Linda JamesAug 31, 2025
      Faulty indication of capacity control position in your mycom Air Compressor may arise from imprecision in the compressor indicator. Manually tighten screws to the 0% indication position of compressor capacity control. It could also be due to imprecision in the controller capacity control indicator, in which case, replace the indicator cam. Another potential cause is a malfunction in the potentiometer; if this is caused by aging degradation or prolonged partial load operation, replace the potentiometer.
  • B
    butlergloriaSep 4, 2025
    What causes capacity control malfunction in my mycom 220JS-V Air Compressor?
    • D
      Daniel MedinaSep 4, 2025
      Capacity control malfunction in your mycom Air Compressor can occur if 100% or 0% is undetected by the indicator; replace the micro-switch in this case. Malfunction of solenoid (modular) valves or related relays for capacity control can also cause this issue; for aging degradation, replace the parts. Internal leakage of solenoid (modular) valves for capacity control is another possibility; if caused by prolonged low load operation, improve by re-examining the operation method.
  • S
    Stephen HobbsSep 7, 2025
    How to address abnormal vibration and/or noise in my mycom Air Compressor?
    • D
      Donna NelsonSep 7, 2025
      Abnormal vibration or noise in your mycom Air Compressor might be due to insufficient axis adjustment with the motor side; readjust the shaft-center. Another cause could be a large runout in the Male rotor axis; if loose locknuts exist and no other fault is found in parts such as the thrust bearing, tighten the locknuts evenly. Damage to the thrust bearing can also result in abnormal vibration or noise. Note that the appropriate time for replacement will differ due to operating conditions.
  • K
    Kirsten MooreNov 11, 2025
    Why is my mycom 220JS-V Air Compressor not starting?
    • A
      Angela JonesNov 11, 2025
      Several factors can prevent your mycom Air Compressor from starting. The power source might be off, so it is recommended to check using a check sheet, and by pointing and calling. There may be a main motor malfunction (refer to the motor instruction manual for other causes and actions), a capacity control of 0% undetected by the unloader indicator (replace the micro-switch), a capacity control hydraulic circuit defect (readjust), leaks or clogging in pipes and solenoid valves (remove factors, check oil contamination level, and replace pipes and solenoid valves). Other potential causes include unconfirmed hydraulic pressure or cooling water circulation (identify malfunctioning devices, examine their causes, take measures, and replace malfunctioning devices), clogging in connecting pipes (re...
  • P
    pmyersNov 22, 2025
    What causes low oil-supply pressure in my mycom 220JS-V Air Compressor?
    • P
      Patrick JohnsonNov 22, 2025
      Low oil-supply pressure in your mycom Air Compressor can stem from several causes. There might be clogging in the oil filter element, indicated by a big difference in outlet/inlet pressures; remove the clogging, check the oil contamination level, and change the lubricant if necessary. A defect inside the compressor could also be responsible; check the oil contamination level and, after a vibration noise diagnosis, overhaul the compressor if necessary. Other potential causes include insufficient oil amount in the oil separator (inspect the oil heater and related circuit relays, replacing parts as needed), insufficient return due to insufficient refrigerant circulation (resolve the refrigerant circulation issue and return oil from the load side heat exchanger), or an extensive oil leak (insp...
  • D
    David CoxNov 25, 2025
    How to troubleshoot a leak from the mechanical seal of my mycom 220JS-V?
    • K
      Kyle SmithNov 26, 2025
      If there's a leak from the mechanical seal of your mycom Air Compressor, it could be an initial leak after replacement until the sliding surfaces fit together. For an initial leak, the amount might increase temporarily but should gradually decrease; monitor to ensure it doesn't continuously increase. Another cause is damaged sliding surfaces due to excessive heat; if the heat load is below the device’s design conditions, re-examine operating conditions. Deteriorated parts, such as an aging O-ring, can also cause leaks, so replace the O-ring. Finally, incompatibility between operating conditions (working temperature ranges, refrigerant, etc.) and the lubricant could be the issue; re-examine operating conditions if possible, and if not, select a suitable lubricant and replace all the current...

Summary

Important Information for Safe Use

Safety

Observation;Prevention

Details essential do's and don'ts for safe operation and maintenance.

Safety Devices

Describes the function, inspection, and importance of safety devices for compressor protection.

Structure and Specifications

Compressor Specifications

Provides detailed technical specifications for 170J, 220J, and 280J series compressors.

Mechanisms and Control

Installation

Lubricant (Refrigerant Oil) Charge

Provides detailed procedures for initial and additional lubricant charging.

Compressor and Package Operation

Lubricant Management and Selection

Provides guidelines for selecting, managing, and handling lubricant for compressor performance.

Precautions for Operation

Explains liquid return prevention and purging of non-condensable gases.

Maintenance and Inspection

Precautions for Maintenance and Inspection

Outlines crucial safety measures and general precautions before performing maintenance.

Disassembly and Assembly of the Compressor

Provides detailed procedures and precautions for disassembling and reassembling compressor components.

Troubleshooting

Troubleshooting Guide

Lists common compressor troubles, direct causes, factors, and recommended actions for resolution.