J
jdavisAug 17, 2025
What causes abnormally high pressure in my mycom Air Compressor?
- SStephanie SimpsonAug 17, 2025
Abnormally high pressure in your mycom Air Compressor can be caused by a heat exchange failure at the condenser (heat exchanger). Clean and wash the heat exchangers, using solvent depending on the contamination. Other causes include malfunction of the fan motor, thermo-switch, water spray bars, cooling water pumps, etc. (identify malfunctioning devices, examine their causes, take measures, and replace malfunctioning devices), a flow volume adjustment fault for cooling water, brine, etc. (readjust manually or examine the cause and take measures if an automatic control valve is used), or poor performance in the heat exchanger (re-examine the conditions to improve if the trouble is caused by a change in operating conditions).