17
5. Start-Up/Shut-Off the Battery Module
5.1 Start up the battery module
1. When battery module is in the shutdow mode, press manual
ON/OFF button for 5 secs.
2. Or, simply turn on the the power module and connect battery module to
operating power module. The battery module will be automatically turned on.
5.2 Shut-off the battery module
1. When battery module is in the operating mode, press manual ON/OFF button
for 5 secs.
2. Or, if battery module is not operated (charge or discharge) for 10 hours, the
battery module will automatically shut off.
3. Or, the battery module has no connection to the system (power module).
After operates without any connection with the COM Port (RS-485) for 24
hours, the battery will shut-off automately.
4. Or, the battery module is removed from the power module after 24 hours, the
battery will shut-off automately.
5. Or, when the cell voltage is lower than 2.3V/Cell for 10 minutes, the battery
module will shut-off.