This section helps you to understand the different problems that may arise on your generating set. The safest way
to correct the problems you may encounter, however, is to contact a qualied engineer. Some operations must be
carried out by a qualied Nanni Diesel authorised engineer. These operations are marked in bold in the tables below.
This non-exhaustive list serves as a tool in emergencies and should never be considered a repair procedure. Some
of the components listed may not be part of your engine.
Faults and probable causes
Engine does not start / starter does not turn
Faults Solution
Circuit breaker is open or fuse has blown
Check and re-install the circuit breaker or replace
the fuse or replace the circuit breaker
Electrical circuit breaker is not working
Electrical connections are faulty
Check the electrical connections and wires (especially
the battery cables) Clean and tighten the connections
Battery faulty Test and charge or replace the battery if faulty
Starting procedure defective Read and implement the starting procedure
Fuel tank empty or fuel cock closed Fill the tank or open the cock
Fuel pump faulty Replace the pump
Fuel lters clogged or water present
Clean or replace the fuel lters or drain the water from
the prelter then drain the circuit
Fuel contaminated or too old Drain the tank if contaminated and ll with clean fuel
Fuel pipe or air pipe of tank blocked or bent
Replace the bent pipes or blow in compressed air
to remove the obstruction
Air present in fuel injection system Drain the injection system
23
Troubleshooting