NAPCO Gemini C-Series Control Panel Installation Instructions--Volume 2
Installation Instructions, Volume 2 Page 55
Memory Fail - A User or Dealer Memory error will cause the sounder to pulse, the "SYS/TBL" reminder to flash, and the dis-
play to indicate an E19 or E20 memory error.
System Low Battery - An E02 system battery trouble is generated when there is either a depleted or damaged battery and/or
the battery charging circuit is not working correctly.
AC Fail - An E01 AC power failure / brownout trouble is generated when AC power is absent from the system (or low volt-
age).
EZM Tamper - A GEMC-EZM8 Zone Expansion Module cover was removed, causing an E13 EZM Tamper trouble.
Sensor Watch - This feature can be used for any zone containing a PIR or dual-technology sensor, floor mats, door contacts,
or other device where some activity is expected. Program this feature to supervise the sensor by verifying that the zone
activates before the PIR timer runs out. If no trip is detected within the programmed Sensor-Watch time, a "E22-NN PIR
SENSOR TRBL" system trouble will result.
Telco Fault 1 - Enable Telephone Line 1 Fault Test will cause the panel to monitor telephone line 1. A failure will indicate
an E08 telephone line trouble. For Burglary systems, this system trouble is used to activate the Burglary Bell. System
trouble displays after a programmed delay of low on hook voltage and no off hook line current from connected phone line.
Telco Fault 2 - Enable Telephone Line 2 Fault Test will cause the panel to monitor telephone line 2. (See "Telco Fault 1"
above).
Digital Dialer Test - This keypad Function Menu feature (TEST COMMUNICATOR) will send a programmed report code to the
central station. Note that in this case the report code received is not indicative of a system trouble, but is an indication of a
successful transmission. Should the transmission fail, the keypad will indicate an E03 communication failure (the trouble
will clear after any successful subsequent report).
Service Message - A service message can be programmed through the PCD-Windows Quickloader Event-Schedule screen
to remind the user to arrange for scheduled maintenance. At the programmed date and time, the keypad sounder will
pulse and display will indicate an E24 "Time for Service" message.
Program Change - If enabled, the panel will report to the central station when the panel receives a download from the Quick-
loader (change of program), or exits a keypad dealer program mode. Select option by enabling the "Program
Change" (located in the System Assignment screen, System Reporting/Outputs tab). Required in Fire reporting ac-
counts.
RF Receiver Trouble - An trouble is generated when the wireless receiver or SLC module is not responding.
Wireless Tamper - An E15 "Wireless RF Transmitter or SLC Point cover removed" is indicated. The unit may be re-
moved from its mounting location and/or an SLC device cover is removed.
Wireless Trouble - Any wireless trouble was indicated.
Keypad Fail - An E10 "Burglary keypad or ACM response failure" or E32 "Fire keypad response failure" keypad re-
sponse failure is generated.
EZM Fail - An E12 "Burg Expansion Zone Module response failure" or E31 "Fire Expansion Zone Module response fail-
ure" is indicated.
QL Device Control - A status change for any output shown in the Quickloader Status/Control screen (click Panel History,
Status History, then click the Output Status tab; the Relay Output Control button is located at the bottom of this
screen).
Gen. Alarm - Any alarm was tripped.
Communications Failure - An E03 communication failure trouble (system not able to report to the central station) is indi-
cated.
Burg Module - An E62 Burglary Module (GEMC-BM or GEMC-BM/PS) response trouble is indicated.
Burg SLC Trouble - Any GEMC-BSLC trouble is indicated.
Burg SLC Point Trouble - A Burglary GEMC-BSLC device trouble is indicated
Burg Module Low Battery - An low battery is detected on the battery connected to the GEMC-BM/PS Burg Module.
Relay Group 1-8 - A device status change within a relay group occurred.
Entry Relay Area 2-8 - A change in status of an entry relay/output (an external output/relay programmed to trip upon entry) is
indicated.
Area 2-8 Disarm - Areas 2, 3, 4, 5, 6, 7, or 8 was disarmed.
Area 2-8 Armed Away - Areas 2, 3, 4, 5, 6, 7, or 8 was armed "AWAY".
Report Telco 1
Report Telco 3 (Dual or Split Reporting)
Alarms, alarm restores, troubles and trouble restores may be selected individually for each zone. Violation of a zone selected
to report will communicate the code(s) selected for that zone to the central station.
Normally, Report Telco 1 is used to report to the central station. Report Telco 3 is used when certain zones will report to a
different receiver (split reporting); Report Telco 1 and Report Telco 3 are both used on the same zone to report to two receiv-
ers successively (Dual Reporting). (Dual Reporting requires a successful report to Telco 1 before reporting to Telco 3). Also
see Backup Report on Telco 2.
Report Zone Wireless Trouble/ Restore to Telco 1
Send Zone Wireless Trouble/ Restore report(s) to Telco 1.
Reset Day Zone/Trouble with Arm/Disarm Only See Day Zone/Trouble
BURGLARY GLOSSARY

Other manuals for NAPCO GEMINI GEMC-96

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the NAPCO GEMINI GEMC-96 and is the answer not in the manual?

NAPCO GEMINI GEMC-96 Specifications

General IconGeneral
BrandNAPCO
ModelGEMINI GEMC-96
CategoryControl Panel
LanguageEnglish

Related product manuals