EasyManuals Logo

Navien NHB-110 Service Manual

Navien NHB-110
147 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #106 background imageLoading...
Page #106 background image
106 NHB Service Manual
Version 1.0
Check method
Fault Possible Causes Check method
110E
Exhaust blockage
Abnormal flow of intake
air supply / exhaust
1. If 110E occurs intermittently during ignition or combustion, compare the
standard RPM with the current RPM at Min / Max combustion (dip switch
1-1&1-2). If the current RPM is higher than normal, check the following:
Air supply / exhaust vent for any blockages.
Blocked condensate drain
If the air pressure sensor hose is broken or clogged.
2. Replace the old PCB with the latest version.
Condensate drain error Condensate drain error
Exhaust air is blocked due to condensate drain error.
Check if the condensate hose or the siphon is frozen.
Check if the condensate hose is kinked.
Remove bottom of trap and verify it is not blocked.
Defective air supply /
exhaust flue
Deformed or clogged flu
1. Check the exterior of the flue for damage and obstructions.
2. Check if rainwater is collected due to vertical installation of the air intake pipe.
Exhaust gas flows in
through the supply pipe
If the exhaust gas enters into the air supply pipe, abnormal combustion may cause
E110.
Check the installation of the flue.

Table of Contents

Other manuals for Navien NHB-110

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Navien NHB-110 and is the answer not in the manual?

Navien NHB-110 Specifications

General IconGeneral
CategoryBoiler
BrandNavien
ModelNHB-110
Maximum Input110, 000 BTU/h
Efficiency95% AFUE
Weight75 lbs
Vent TypeDirect Vent
Fuel TypeNatural Gas or Propane
Heat Exchanger MaterialStainless Steel
Water Connection Size3/4 inch
Gas Connection Size3/4 inch
Vent MaterialPVC, CPVC, Polypropylene
Vent Size2 inch

Related product manuals