EasyManuals Logo

Navien NHB-110 Service Manual

Navien NHB-110
147 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #114 background imageLoading...
Page #114 background image
114 NHB Service Manual
Version 1.0
5.2.17 291Error
Error conditions and Check Items
Error Description
E291
Supply / Return inversion limit
If the return temperature is higher than supply temperature + 10°F (5.5°C)”, the system stops
operation and displays error code (E291) on the front panel.
Check items
1. Check whether the space heating pipe connection is inversed.
2. Check the supply temperature sensor connection.
3. Check the return temperature sensor connection.
Is the space heating pipe
connection normal?
Check the supply and return
temperature sensor
Replace space heating pipe
connection
No
Yes
Check method
Fault Possible Causes Check method
Space heating pipe
connection
Defective connection Check whether the space heating pipe connection is inversed.
Temperature sensor
1. Check the supply temperature sensor connection.
2. Check the return temperature sensor connection.

Table of Contents

Other manuals for Navien NHB-110

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Navien NHB-110 and is the answer not in the manual?

Navien NHB-110 Specifications

General IconGeneral
CategoryBoiler
BrandNavien
ModelNHB-110
Maximum Input110, 000 BTU/h
Efficiency95% AFUE
Weight75 lbs
Vent TypeDirect Vent
Fuel TypeNatural Gas or Propane
Heat Exchanger MaterialStainless Steel
Water Connection Size3/4 inch
Gas Connection Size3/4 inch
Vent MaterialPVC, CPVC, Polypropylene
Vent Size2 inch

Related product manuals