Page 11
-↑ +↓
P401 Exit 4 Work time (10 - 240) s F[60]
-↑ +↓
P402
Exit 4 Reset time (0 - 60)min F[0]
If F[0] the function is not on.
-↑ +↓
P403
Exit 4 Wind sensor function (0 - 2) F[0]. Set the action when active as
follows:
0=none
1=open
2=close
-↑ +↓
P404
Exit 4 Rain sensor function (1 - 2) F[2]. Set the action when the input is
active, as follows:
0=none
1=open
2=close
-↑ +↓
P405
Exit 4 Timer function F[0]. Set the action when active as follows:
0=none
1=open
2=close
-↑ +↓
P406 Exit 4 Aeration time (1-60)min F[10].
-↑ +↓
P407
Exit 4 Single manual command functioning mode:
0=half-automatic mode
1=dead-man mode, sensors and remote controls enabled
2= dead-man mode, sensors and remote controls disabled
-↑ +↓
P501 Exit 5 Work time (10 - 240) s F[60]
-↑ +↓
P502
Exit 5 Reset time (0 - 60)min F[0]
If F[0] the function is not on.
-↑ +↓
P503
Exit 5 Wind sensor function (0 - 2) F[0]. Set the action when active as
follows:
0=none
1=open
2=close
Page 12
-↑ +↓
P504
Exit 5 Rain sensor function (1 - 2) F[2]. Set the action when the input is
active, as follows:
0=none
1=open
2=close
-↑ +
↓
P505
Exit 5 Timer function F[0]. Set the action when active as follows:
0=none
1=open
2=close
-↑ +↓
P506 Exit 5 Aeration time (1-60)min F[10].
-↑ +↓
P507
Exit 5 Single manual command functioning mode:
0=half-automatic mode
1=dead-man mode, sensors and remote controls enabled
2= dead-man mode, sensors and remote controls disabled
-↑ +↓
P601 Exit 6 Work time (10 - 240) s F[60]
-↑ +↓
P602
Exit 6 Reset time (0 - 60)min F[0]
If F[0] the function is not on.
-↑ +↓
P603
Exit 6 Wind sensor function (0 - 2) F[0]. Set the action when active as
follows:
0=none
1=open
2=close
-↑ +↓
P604
Exit 6 Rain sensor function (1 - 2) F[2]. Set the action when the input is
active, as follows:
0=none
1=open
2=close
-↑ +↓
P605
Exit 6 Timer function F[0]. Set the action when active as follows:
0=none
1=open
2=close
-↑ +↓
P606 Exit 6 Aeration time (1-60)min F[10].