MENU 1.30.7 - OWN CURVE
Own curve, cooling
Caution
Curve 0 must be selected for own curve to
apply.
You can create your own cooling curve here, if there are
special requirements, by setting the desired supply
temperatures for different outdoor temperatures.
Supply temp
Setting range: -5 – 40 °C
Depending on which accessory is used the setting range
can vary.
MENU 4.2.3 - SG READY
Affect cooling
With low price mode of "SG Ready" and cooling opera-
tion the indoor temperature is not affected.
With over capacity mode on "SG Ready" and cooling
operation, the parallel offset for the indoor temperature
is reduced by "-1". If a room sensor is installed and activ-
ated, the desired room temperature is instead reduced
by 1 °C.
MENU 4.2.5 - SMART PRICE ADAPTION™
Affect cooling
Alternative: on/off
Degree of effect
Setting range: 1 - 10
This function can only be used if your electricity supplier
supports Smart price adaption, if you have an hourly
tariff agreement and an active myUplink account.
Smart price adaption™ moves the heat pump's consump-
tion over 24 hours to periods with the cheapest electri-
city tariff, which gives savings for hourly rate based
electricity contracts. The function is based on hourly
rates for the next 24 hours being retrieved via myUplink
and therefore an internet connection and an account for
myUplink are required.
You can choose which parts of the installation are to be
affected by the electricity price and to what extent; the
higher value you select, the greater the effect the elec-
tricity price has.
NOTE
A value that is set high may result in increased
savings, but may also affect the comfort.
MENU 7.1.2.2 - PUMP SPEED HEATING
MEDIUM GP1
Make settings here for the heating medium pump's
speed in the current operating mode, for example in
heating or hot water operation. Which operating modes
can be changed depends on which accessories are
connected.
Minimum permitted speed
Setting range: 1 - 50 %
Speed in standby mode
Setting range: 1 - 100 %
Speed during active cooling
Setting range: 1 - 100 %
Highest permitted speed
Setting range: 50- 100%
Minimum permitted speed: Here you can restrict the
pump speed so that the heating medium pump is not
allowed to operate at a lower speed than the set value.
Speed in standby mode: The speed the heating medium
pump is to have in standby mode is set here. Standby
mode occurs when heating or cooling operation is per-
mitted at the same time as there is no need for either
compressor operation or electric additional heat.
Speed during active cooling: Here, you set the desired
pump speed for active cooling.
Maximum permitted speed: Here you can restrict the
pump speed so that the heating medium pump is not
allowed to operate at a higher speed than the set value.
MENU 7.1.2.7 - PUMP SPEED BRINE
Make settings for the brine pump's speed here.
Operating status
Setting range: Fixed delta, Auto, manual
Manual
Setting range: 1 - 100 %
Speed during active cooling
Setting range: 1 - 100 %
Delta-T cooling
Setting range: 2 - 10 °C
Speed in standby mode, cooling
Setting range: 1 - 100 %
Speed in passive cooling
Setting range: 1 - 100 %
Speed in standby mode, cooling
Setting range: 0 - 100 %
ACS 45 | GB26