PROGRAM SETTINGS
Activating AXC 30 can be performed via the start guide
or directly in the menu system.
START GUIDE
The start guide appears upon first start-up after heat
pump installation, but is also found in menu 7.7.
MENU SYSTEM
If you do not make all settings via the start guide or need
to change any of the settings, this can be done in the
menu system.
Menu 7.2.1 - Add/remove accessories
Here, you state which accessories are installed for the
compatible product.
To identify connected accessories automatically, select
"Search for accessories". It is also possible to select ac-
cessories manually from the list.
Menu 1.1 - Temperature
You make temperature settings for your installation here.
Menu 1.3 - Room sensor settings
Here, you make your settings for room sensors and
zones. The room sensors are grouped by zone.
Here, you select the zone to which a sensor will belong.
It is possible to connect multiple room sensors to each
zone. Each room sensor can be given a unique name.
The control of heating, cooling, humidity and ventilation
are activated by ticking each option. Which options are
shown depends on which type of sensor is installed. If
control is not activated, the sensor will be the displaying
sensor.
Caution
A slow heating system such as underfloor
heating may be inappropriate for controlling
with room sensors.
Menu 1.30.7 - Own curve
Own curve, heat
Caution
Curve 0 must be selected for own curve to
apply.
You can create your own heating curve here, if there
are special requirements, by setting the desired supply
temperatures for different outdoor temperatures.
Supply temp
Setting range: 5 – 80 °C
Own curve, cooling
Caution
Curve 0 must be selected for own curve to
apply.
You can create your own cooling curve here, if there are
special requirements, by setting the desired supply
temperatures for different outdoor temperatures.
Supply temp
Setting range: -5 – 40 °C
Menu 7.2.4 - Extra climate system (ECS)
Use in heating mode
Setting range: on/off
Use in cooling mode
Setting range: on/off
Shunt amplification
Setting range: 0.1 – 10.0
Shunt waiting time
Setting range: 10 – 300 s
Contr. pump GP10
Setting range: on/off
Control signal
Setting range: PWM / 0-10V*
Manual speed
Setting range: 0 – 100%
Factory setting: 70%
*Factory setting
The shunt amplification and shunt waiting time for the
different extra climate systems that are installed are
also set here.
Menu 7.5.3 - Forced control
Here you can force control the various components in
the installation. The most important safety functions
remain active however.
NOTE
Forced control is only intended to be used for
troubleshooting purposes. Using the function
in any other way may cause damage to the
components in your climate system.
Caution
Also see the Installer Manual for the main
product.