LOW SYSTEM PRESSURE
Not enough water in the climate system.
Fill the climate system with water and check for
leaks. In event of repeated filling, contact the in-
staller.
COMPRESSOR DOES NOT START
There is no heating requirement.
F1355 does not call on heating or hot water.
Compressor blocked due to the temperature condi-
tions.
Wait until the temperature is within the product’s
working range.
Minimum time between compressor starts has not
been reached.
Wait for at least 30 minutes and then check if the
compressor has started.
Alarm tripped.
Follow the display instructions.
WHINING NOISE IN THE RADIATORS
Closed thermostats in the rooms and incorrectly set
heating curve.
Set the thermostats to max. in as many rooms as
possible. Adjust the heating curve via menu 1.1, in-
stead of choking the thermostats.
Circulation pump speed set too high.
Enter menu 5.1.11 (pump speed heating medium)
and reduce the speed of the circulation pump.
Uneven flow over the radiators.
Adjust the flow distribution between the radiators.
NIBE F1355Chapter 5 | Disturbances in comfort54