room sensor settings
room sensor settings 1.9.4
factor system 1
control room sensor syst 2
control room sensor syst 3
factor system 3
control room sensor syst 1
control room sensor syst 4
factor system
heating
Setting range: 0.0 - 6.0
Default value: 2.0
Menu
1.9.4
Room sensors to control the room temperature can be activated here.
Caution
A slow heat-releasing heating system, such as for example, underfloor
heating, may not be suitable for control using the heat pump's room
sensor.
Here you can set a factor (a numerical value) that determines how much
an over or sub normal temperature (the difference between the desired
and actual room temperature) in the room is to affect the supply temper-
ature to the climate system. A higher value gives a greater and faster
change of the heating curve's set offset.
NOTE
Too high a set value for "factor system" can (depending on your climate
system) produce an unstable room temperature.
If several climate systems are installed the above settings can be made for
the relevant systems.