op. prioritisation
Setting range: 0 to 180 min
Default value: 30 min
Choose here how long the heat pump should work with each requirement
if there are two requirements at the same time. If there is only one require-
ment the heat pump only works with that requirement.
The indicator marks where in the cycle the heat pump is.
If 0 minutes is selected it means that requirement is not prioritised, but
will only be activated when there is no other requirement.
Menu
4.9.1
auto mode setting
stop heating
Setting range: -20 – 40 °C
Default values: 15
stop additional heat
Setting range: -25 – 40 °C
Factory setting: 5
filtering time
Setting range: 0 – 48 h
Default value: 24 h
Menu
4.9.2
When the operating mode is set to "auto", the heat pump selects when
start and stop of additional heat and heat production is permitted, depend-
ent on the average outdoor temperature.
Select the average outdoor temperatures in this menu.
You can also set the time over which (filtering time) the average temper-
ature is calculated. If you select 0, the present outdoor temperature is
used.
NIBE™ F750Chapter 3 | F750 – at your service66