Nidec NE300-4T0110G/0150PB - User Manual

Nidec NE300-4T0110G/0150PB
244 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
Serial No -3101A003
User Manual
NE200/NE300
High performance
vector control drive
Scan QR to follow us

Table of Contents

Other manuals for Nidec NE300-4T0110G/0150PB

Questions and Answers

  • S
    schmidtlisaSep 23, 2025
    What to do if Nidec NE300-4T0110G/0150PB show EEPROM error?
    • J
      john21Sep 23, 2025
      If your Nidec DC Drives are showing an EEPROM error: 1. Recover factory defaults if function code parameter writing error. 2. Ask for service from supplier, if EEPROM damaged.
  • R
    Robert AlvarezAug 23, 2025
    What causes over current in Nidec DC Drives during acceleration and how to fix it?
    • E
      Eric SmithAug 25, 2025
      Overcurrent during acceleration in Nidec DC Drives can stem from a few reasons. If the acceleration time is too short, increase it. Also, check the input power source for low voltage. Finally, if the drive power rating is too small, choose a drive with higher capacity.
  • G
    Gina LiAug 25, 2025
    What causes over current at constant-speed in Nidec NE300-4T0110G/0150PB DC Drives?
    • K
      Kelly PattersonAug 26, 2025
      If you're experiencing overcurrent at a constant speed with your Nidec DC Drives, several factors could be the cause. Check the load for any abnormal mutations. Also, verify the input power source isn't experiencing low voltage. Ensure your drive has sufficient power capacity. Finally, if you're using closed-loop vector control, inspect the encoder and its wiring for any sudden disconnections.
  • R
    Robert LamAug 26, 2025
    What to do if Nidec NE300-4T0110G/0150PB show drive overload?
    • C
      Charles GonzalezAug 27, 2025
      If your Nidec DC Drives are showing a drive overload, first check the input power source for low voltage. If the load is too heavy, select a drive with a bigger capacity. If the acceleration is too fast, increase the acceleration time. Also, avoid restarting the motor while it's still turning.
  • F
    floressamanthaAug 27, 2025
    What causes over current in Nidec NE300-4T0110G/0150PB DC Drives during deceleration?
    • J
      Jordan PierceAug 27, 2025
      Overcurrent during deceleration in Nidec DC Drives can occur due to several reasons. If the deceleration time is too short, increase it. If there is a large load inertia, add suitable brake devices. Finally, if the drive power rating is too small, choose a higher capacity drive.
  • J
    Julie SwansonSep 16, 2025
    What to do if Nidec DC Drives show keypad & control board communication interrupted?
    • K
      Karen Blackburn MDSep 16, 2025
      If communication between the keypad and control board is interrupted on your Nidec DC Drives, check the connection cable between the keypad and control panel.
  • R
    randallfernandezSep 13, 2025
    What to do if Nidec DC Drives show external terminal fault?
    • R
      Rachel RodriguezSep 13, 2025
      If your Nidec DC Drives are showing an external terminal fault, check the external input, as the fault likely originates from the external control circuit.
  • J
    Jesse ScottSep 14, 2025
    What to do if Nidec NE300-4T0110G/0150PB show Parameter copy Error?
    • G
      Glenda GarciaSep 15, 2025
      If your Nidec DC Drives are showing a Parameter copy Error: 1. Shorten the cable between Keypad and control board to reduce interference if too long connection cable between keypad and control board leads to interference in parameters transmission. 2. Before downloading, make sure the parameters match the drive, if the downloading parameters do not match the existed parameters in the drive.
  • A
    Anthony StoneSep 5, 2025
    What to do if Nidec NE300-4T0110G/0150PB DC Drives show ground fault?
    • R
      robert10Sep 5, 2025
      If your Nidec DC Drives are indicating a ground fault, it could be due to a short circuit in one of the output phases. Check whether the electric motor insulation is weakening. Also, check whether the wiring between the frequency converter and the electric motor is damaged.
  • J
    joshua12Sep 3, 2025
    What to do if Nidec DC Drives show fast current limit fault?
    • K
      Kristy WoodSep 3, 2025
      If your Nidec DC Drives are showing a fast current limit fault, it could be due to a load that is too large or a motor blocked to stall, so decrease the load and check the motor and mechanical part status. If the drive power rating is too small, choose a higher power drive. If the drive output circuit loop is grounded or short-circuited, remove the external fault.

Summary

Chapter 1 NE200;300 Product Introduction

1.4 Specifications

Provides detailed technical specifications for NE200 and NE300 drives.

Chapter 3 Wiring

3.1 Connection of the Product and Peripheral Devices

Diagram showing connections of the drive and peripheral devices.

3.5 Attention for Main Circuit Wiring

Important notes and precautions for main circuit wiring.

3.6 Control Terminal Wiring

Wiring diagrams for control terminals of NE200 and NE300 drives.

Chapter 4 Operation and Display

4.1 Keypad

Describes the drive keypad types, buttons, and indicators.

4.2 Function Code Viewing and Modification

Explains the menu structure and process for viewing/modifying function codes.

Chapter 5 Parameters Brief

F1: Start and Stop Control

Details parameters for start/stop modes, DC brake, and acceleration/deceleration.

F2: Auxiliary Running Function

Details parameters for jog operation, skip frequency, and anti-reverse control.

F3 Vector Control Parameters

Details speed loop PI, current loop, and torque control parameters for vector control.

F4: V;F Control Parameters

Details V/F curve settings, torque boost, and slip compensation parameters.

F5: Motor Parameters Group

Details motor type, rated power, current, speed, and impedance parameters.

F8: PID Parameters

Details PID setup, feedback channels, and control parameters.

FC: Protection and Fault Parameters Group

Details motor overload, current limit, and phase loss protection parameters.

FF: Running History Record Group

Details fault history, total power on time, and software versions.

FP Protection Parameters

Details user password, parameter write-in, and upload protection settings.

Chapter 6 Parameter Description

6.2 Start and Stop Group (F1)

Details parameters for start/stop modes, DC brake, and acceleration/deceleration.

6.4 Vector Control Parameters (F3)

Details speed loop PI, current loop, and torque control parameters for vector control.

6.9 PID Parameters (F8)

Details PID setup, feedback channels, and control parameters.

6.13 Protection and Fault Parameters Group (FC)

Details motor overload, current limit, and phase loss protection parameters.

6.16 Running History Record Group (FF)

Details fault history, total power on time, and software versions.

6.17 Protection Parameters (FP)

Details user password, parameter write-in, and upload protection settings.

Chapter 7 Fault Information and Trouble Shooting

7.1 Fault Information and Solutions

Lists common faults, their causes, and solutions.