Nidec NE300-4T0370G/0450P - User Manual

Nidec NE300-4T0370G/0450P
244 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
Serial No -3101A003
User Manual
NE200/NE300
High performance
vector control drive
Scan QR to follow us

Table of Contents

Other manuals for Nidec NE300-4T0370G/0450P

Questions and Answers

  • J
    Jenny WaltersSep 23, 2025
    What to do if Nidec NE300-4T0370G/0450P DC Drives show EEPROM error?
    • F
      figueroakatherineSep 23, 2025
      If your Nidec DC Drives are showing an EEPROM error: 1. Recover factory defaults if function code parameter writing error. 2. Ask for service from supplier, if EEPROM damaged.
  • M
    Michelle BarnesAug 23, 2025
    What causes over current in Nidec NE300-4T0370G/0450P DC Drives during acceleration and how to fix it?
    • M
      Michael AndersonAug 23, 2025
      Overcurrent during acceleration in Nidec DC Drives can stem from a few reasons. If the acceleration time is too short, increase it. Also, check the input power source for low voltage. Finally, if the drive power rating is too small, choose a drive with higher capacity.
  • M
    Melissa BassAug 25, 2025
    What causes over current at constant-speed in Nidec DC Drives?
    • B
      Barry BoyleAug 26, 2025
      If you're experiencing overcurrent at a constant speed with your Nidec DC Drives, several factors could be the cause. Check the load for any abnormal mutations. Also, verify the input power source isn't experiencing low voltage. Ensure your drive has sufficient power capacity. Finally, if you're using closed-loop vector control, inspect the encoder and its wiring for any sudden disconnections.
  • C
    Carrie MontesAug 27, 2025
    What to do if Nidec NE300-4T0370G/0450P show drive overload?
    • K
      Keith HubbardAug 27, 2025
      If your Nidec DC Drives are showing a drive overload, first check the input power source for low voltage. If the load is too heavy, select a drive with a bigger capacity. If the acceleration is too fast, increase the acceleration time. Also, avoid restarting the motor while it's still turning.
  • E
    Eileen WilliamsAug 27, 2025
    What causes over current in Nidec DC Drives during deceleration?
    • J
      James CowanAug 27, 2025
      Overcurrent during deceleration in Nidec DC Drives can occur due to several reasons. If the deceleration time is too short, increase it. If there is a large load inertia, add suitable brake devices. Finally, if the drive power rating is too small, choose a higher capacity drive.
  • C
    Charles SmithSep 16, 2025
    What to do if Nidec DC Drives show keypad & control board communication interrupted?
    • J
      Joshua ShawSep 16, 2025
      If communication between the keypad and control board is interrupted on your Nidec DC Drives, check the connection cable between the keypad and control panel.
  • B
    Belinda PattonSep 13, 2025
    What to do if Nidec NE300-4T0370G/0450P DC Drives show external terminal fault?
    • A
      amberjonesSep 13, 2025
      If your Nidec DC Drives are showing an external terminal fault, check the external input, as the fault likely originates from the external control circuit.
  • P
    Pamela IngramSep 14, 2025
    What to do if Nidec NE300-4T0370G/0450P show Parameter copy Error?
    • S
      Stephanie MayerSep 15, 2025
      If your Nidec DC Drives are showing a Parameter copy Error: 1. Shorten the cable between Keypad and control board to reduce interference if too long connection cable between keypad and control board leads to interference in parameters transmission. 2. Before downloading, make sure the parameters match the drive, if the downloading parameters do not match the existed parameters in the drive.
  • A
    Alan AlexanderSep 5, 2025
    What to do if Nidec DC Drives show ground fault?
    • J
      Jessica HodgeSep 5, 2025
      If your Nidec DC Drives are indicating a ground fault, it could be due to a short circuit in one of the output phases. Check whether the electric motor insulation is weakening. Also, check whether the wiring between the frequency converter and the electric motor is damaged.
  • K
    Kelsey ConleySep 3, 2025
    What to do if Nidec DC Drives show fast current limit fault?
    • D
      Dawn GreenSep 3, 2025
      If your Nidec DC Drives are showing a fast current limit fault, it could be due to a load that is too large or a motor blocked to stall, so decrease the load and check the motor and mechanical part status. If the drive power rating is too small, choose a higher power drive. If the drive output circuit loop is grounded or short-circuited, remove the external fault.

Summary

Safety Information

Use

Provides critical guidelines for the intended and safe use of the drive.

Installation

Details important cautions and instructions for safe product installation.

Wiring

Highlights critical warnings and precautions for electrical wiring safety.

Chapter 1 NE200;300 Product Introduction

1.4 Specifications

Lists detailed technical specifications for NE200 and NE300 drives.

Chapter 2 Installation

Chapter 3 Wiring

3.5 Attention for Main Circuit Wiring

Lists important precautions and considerations for main circuit wiring.

Chapter 4 Operation and Display

4.2 Function code viewing and modification

Explains the multi-level menu structure for viewing and modifying function codes.

Chapter 5 Parameters Brief

Group F1: Start and stop control

Details parameters related to the drive's start and stop operations.

Group F3: Vector Control Parameters

Lists parameters specific to vector control mode for precise motor control.

Group F4: V;F Control Parameters

Outlines parameters for V/F control, including V/F curves and torque boost.

Group F5: Motor parameters group (F5)

Essential parameters for configuring motor characteristics for optimal performance.

Group F8: PID Parameters

Covers parameters for PID control loop tuning and configuration.

Group FC: Protection and fault Parameters

Details motor overload, voltage, current, and phase loss protections.

Chapter 6 Parameter description

6.2 Start and stop group (F1)

Details parameters for start, stop, acceleration, and deceleration modes.

6.4 Vector Control Parameters (F3)

Provides detailed parameters for vector control, including speed and torque.

6.5 V;F Control Parameters (F4)

Lists parameters for V/F control, including V/F curves and torque boost.

6.6 Motor parameters group (F5)

Essential parameters for configuring motor characteristics for optimal performance.

6.9 PID Parameters (F8)

Covers PID control parameters for loop tuning and configuration.

6.13 Protection and fault parameters group (FC)

Details motor overload, voltage, current, and phase loss protections.

Chapter 7 Fault information and trouble shooting

7.1 Fault information and solutions.

Lists common trip codes, possible causes, and recommended solutions.

7.2 Warning information

Describes warning codes, their types, and descriptions.

7.3 The general fault diagnosis and solutions

Provides a table for diagnosing common abnormalities and their countermeasures.

Chapter 8 Routine Repair and Maintenance

Appendix B: Modbus Communication Protocol

Nidec NE300-4T0370G/0450P Specifications

General IconGeneral
Input Voltage3-Phase 380-480VAC
Output Power370kW (NE300-4T0370G), 450kW (NE300-4T0450P)
Output Current740A (NE300-4T0370G), 900A (NE300-4T0450P)
Input Frequency50/60 Hz
Cooling MethodForced Air Cooling
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Short Circuit
Storage Temperature-20°C to 65°C