EasyManua.ls Logo

nLight nPP16 ER EFP - User Manual

nLight nPP16 ER EFP
9 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
1 of 3
nPP16 ER EFP
UL-924 EMER. RELAY PACK
FAMILY INSTRUCTIONS
Acuity Brands | One Lithonia Way Conyers, GA 30012 Phone: 800.535.2465 www.acuitycontrols.com © 2018 Acuity Brands Lighting, Inc. All rights reserved. Rev.
01/26/2019 IS-NPP16ER-EFP-004
Electrical Specifications Input Ratings 120/277VAC, 50/60 Hz
120/347VAC, 50/60 Hz (with 347 option)
120-277VAC, 50/60 Hz Normal Power Sense
120-347VAC, 50/60 Hz Normal Power Sense (with 347 option)
Output Ratings 120/277VAC (120/347VAC with 347 option), 50/60 Hz, 16A - Tungsten,
Standard Ballast, Electronic Ballast, General Purpose
120VAC, 50/60 Hz, 1HP - Motor
SCCR: 5KA
100mA, 0-10VDC Dimming Sink Current
Relay Type Latching
Low Voltage Output Ratings Self-powering, does not supply nLight bus voltage
Class Rating 0-10V Dimming can be wired Class 1 or 2
Standards/ Ratings Energy Management Equipment, UL916 (E167435)
Emergency Lighting and Power Equipment, UL924 (E342232)
Mechanical Dimensions 3.38” H x 2.53” W x 1.83” D (86mm x 64mm x 47mm) - does not include ½” chase nipple
Mounting 1/2” Knockout (7/8" hole)
Color Red
Connection Type RJ-45 nLight Network Ports (2)
Non-Dimming Model: Line Voltage Leads
Dimming Model: Line and Low Voltage Leads
Environmental Warrantied Operating Temperature Standard: 14º to 122º F (-10º to 50º C)
LT Option: -4º to 122º F (-20º to 50º C)
Relative Humidity Up to 90%, Non-Condensing
Standards/ Ratings RoHS, Plenum UL2043
SPECIFICATIONS (NPP16 ER EFP)
WARRANTY
5-year limited warranty. Complete warranty terms located at
www.acuitybrands.com/CustomerResources/Terms_and_conditions.aspx
C US LISTED
READ AND FOLLOW ALL SAFETY INSTRUCTIONS!
SAVE THESE INSTRUCTIONS AND DELIVER TO OWNER AFTER INSTALLATION
Question and Answer IconNeed help?

Do you have a question about the nLight nPP16 ER EFP and is the answer not in the manual?

Summary

SPECIFICATIONS (NPP16 ER EFP)

Electrical Specifications

Details input/output ratings, relay type, class, and standards for the device.

Mechanical

Covers dimensions, mounting type, color, and connection types for the device.

Environmental

Outlines operating temperature, humidity, and relevant standards for the device.

INSTALLATION INSTRUCTIONS

TROUBLESHOOTING (NPP16 ER EFP)

Provides guidance for common issues like no power or rapid flashing LEDs.

PROGRAMMING INSTRUCTIONS

A-LEVEL PROGRAMMING INSTRUCTIONS

Steps for entering and setting A-Level programming functions via push-button.

A-LEVEL DETAILED FUNCTION TABLES

Specific A-Level functions for dimming offset and occupied/unoccupied levels.

B-LEVEL PROGRAMMING INSTRUCTIONS

Steps for entering and setting B-Level programming functions via push-button.

B-LEVEL DETAILED FUNCTION TABLES

Specific B-Level functions for tracking channels and operating modes.

FUNCTION 18 DEFINITIONS

Detailed definitions for Special Operating Modes under Function 18.

nLight nPP16 ER EFP Specifications

General IconGeneral
ModelnPP16 ER EFP
Relay TypeElectromechanical
Coil Voltage24 VDC
Mechanical Life10, 000, 000 cycles
Contact FormNormally Open (NO)
Switching Voltage240 VAC
Electrical Life100, 000 cycles