5 Parameter
BU 0240 en-US-4920 73
Parameter list - inverter information (selection)
Parameter Description Settings/functions (selection)
P700
Current operating
status
Display of current messages on the actual
operating status of the variable frequency drive
such as faults, warnings or the cause of a switch-
on block.
Selection:
Current fault (P700, [-01])
Current warning (P700, [-02])
Reason for switch-on block (P700), [-03])
Error group:
1 / 2 = inverter/motor overtemperature
3 / 4 = overcurrent fault
5 = overvoltage fault
16 = phase monitoring motor
19…= error in parameter identification
P701
Last error
Displays the last 5 variable frequency drive faults.
Selection:
Last fault (P701), [-01])
Penultimate fault (P701, [-02])
See P700
P707
Software version
Displays the firmware version/Inverter revision
Selection:
Software version (P707, [-01])
P708
Status of digital
input
Shows the switching status of the digital inputs.
Bit 1 = DIN 2
P709
Voltage of analog
input
Displays the measured analog input value.
Input selection:
Potentiometer P1 (P400, [-01]) - SK 2x5E
Potentiometer P2 (P400, [-02]) - SK 2x5E
AIN1 (P400, [-01]) - SK 2x0E
AIN2 (P400, [-02]) - SK 2x0E
DIN 2 (P400, [-06])
Actual current
Displays the actual output current.
P740
Process data bus
in
Displays the actual control word and the setpoints.
[-01] = STW (source P509)
[-02…-04] SW 1…3 (source P510[-01]
[-11…-13] SW 1…3 (source P510[-02]
P749
State of DIP
switch
Displays the actual DIP switch setting (S1).
Bit 1 = DIP switch 2
Pos: 642 /A nleit ung en/El ek tr onik /FU und Star ter /6. M eldung en zum B etrie bsz ust and /_M eldu nge n z um Betri ebs zus tan d_0 1 (Üb ers chr ift + Inh alt) [ SK xxx E] @ 3\mod_1361795506047_14638.docx @ 59690 @ 1555 @ 1