NORDAC FLEX (SK 200E ... SK 235E)Users Manual for Frequency Inverters
148 BU 0200 en-3118
Pos: 33 5 /Anlei tung en/El ektr onik/FU und Star ter/5 . Par amet er/ Par amet erau fli st ung (P 000 .. .)/P 200- P299 /Par amet er P203 M otor Ne nnstr om @ 0\mod_1327588500455_388.docx @ 7930 @ @ 1
P203
Nominal motor current
(Nominal motor current)
S P
0.1 ... 1000.0 A
{ see information }
The nominal motor current is a decisive parameter for the current vector control.
Information
Default setting
The default setting is dependent upon the FI nominal power and the setting in P200.
Pos: 33 6 /Anlei tung en/El ektr onik/FU und Star ter /5. Par a meter/ Par a meter auf list ung (P0 00 . ..) /P2 00- P299/ Para meter P2 04 Mo tor Nenns pan nung @ 0\ mod_1327588687111_388.docx @ 7953 @ @ 1
P204
Nominal motor voltage
(Nominal motor voltage)
S P
100 ... 800 V
{ see information }
The >Nominal voltage< matches the mains voltage to the motor voltage. In combination with the
nominal frequency, the voltage/frequency characteristic curve is produced.
Information
Default setting
The default setting is dependent upon the FI nominal power and the setting in P200.
Pos: 33 7 /Anlei tung en/El ektr onik/FU und Star ter/5 . Par ameter/ Par ameter aufli stung (P000 .. .)/P2 00-P2 99/Par amet er P205 Motor N ennlei stung @ 0\mod_1327588736705_388.docx @ 7976 @ @ 1
P205
Nominal motor power
(Nominal motor power)
P
0.00 ... 250.00 kW
{ see information }
The motor nominal power controls the motor set via P200.
Information
Default setting
The default setting is dependent upon the FI nominal power and the setting in P200.
Pos: 33 8 /Anlei tung en/El ektr onik/FU und Star ter/5 . Par amet er/ Par amet erau fli st ung (P 000 .. .)/P 200- P299 /Par amet er P206 M otor cos p hi @ 0\mod_1327588784877_388.docx @ 7999 @ @ 1
P206
Motor cos phi
(Motor cos
ϕ
)
S P
0.50 ... 0.95
{ see information }
The motor cos ϕ is a decisive parameter for the current vector control.
Information
Default setting
The default setting is dependent upon the FI nominal power and the setting in P200.
Pos: 33 9 /Anlei tung en/El ektr onik/FU und Star ter/5 . Par amet er/ Par amet erau fli st ung (P 000 .. .)/P 200- P299 /Par amet er P206 M otor cos p hi_In fo _PM SM @ 19 \mod_1505894620817_388.docx @ 2365524 @ @ 1
Information
PMSM
This parameter is not relevant if a PMSM is used.
Pos: 34 0 /Anlei tung en/El ektr onik/FU und Star ter/5 . Par ameter/ Par ameter aufli stung (P000 .. .)/P2 00-P2 99/Par amet er P207 Motorschaltung @ 0\mod_1327589654065_388.docx @ 8022 @ @ 1
P207
Motor circuit
(Motor circuit)
S P
0 ... 1
{ see information }
0 = star 1 = delta
The motor circuit is decisive for stator resistance measurement (P220) and therefore critical for
current vector control.
Information
Default setting
The default setting is dependent upon the FI nominal power and the setting in P200.