EasyManua.ls Logo

Nord Drivesystems NORDAC FLEX SK 230E Series - Page 206

Nord Drivesystems NORDAC FLEX SK 230E Series
284 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
NORDAC FLEX (SK 200E ... SK 235E)Users Manual for Frequency Inverters
206 BU 0200 en-3118
Pos: 54 7 /Anlei tung en/El ektr onik/FU und Star ter/5 . Par ameter/ Par ameter aufli stung (P000 .. .)/P5 00-P5 99/Par amet er P558 Magneti sier ungsz eit @ 19\ mod_1512376109919_388.docx @ 2374443 @ @ 1
P558
Flux delay
(Flux delay)
S P
0 / 1 / 2 ... 500 ms
{ 1 }
The ISD control can only function correctly if there is a magnetic field in the motor. For this
reason, a DC current is applied before starting the motor to provide the excitation of the stator
winding. The duration depends on the size of the
motor and is automatically set in the factory
setting of the FI.
For time-critical applications, the magnetizing time can be set or deactivated.
0 = Disabled
1 = Automatic calculation
2 ... 500 =Time set in [ms]
NOTE: Setting values that are too low can reduce the dynamics and starting torque.
Pos: 54 8 /Anlei tung en/El ektr onik/FU und Star ter/5 . Par ameter/ Par ameter aufli stung (P000 .. .)/P5 00-P5 99/Par amet er P559 DC-Nachla ufz eit @ 0\ mod_1328098856657_388.docx @ 12215 @ @ 1
P559
DC Run-on time
(DC Run-on time)
S P
0.00 ... 30.00 s
{ 0.50 }
Following a stop signal and the braking ramp, a direct current is briefly applied to the motor to
fully bring the drive to a stop. Depending on the inertia, the time for which the current
is applied
can be set in this parameter.
The current level depends on the previous braking procedure (current vector control) or the static
boost (linear characteristic).
Pos: 54 9 /Anlei tung en/El ektr onik/FU und Star ter/5 . Par ameter/ Par ameter aufli stung (P000 ...) /P5 00-P5 99/Par amet er P560 Param eter Sp eich er mode @ 0 \mod_1328098918376_388.docx @ 12238 @ @ 1
P560
Parameter, Saving mode
(Saving mode parameter)
S
0 ... 2
{ 1 }
0 = Only in RAM, changes to the parameter settings are no longer saved on the EEPROM.
All previously saved settings are retained, even if the FI is disconnected from the mains.
1 = RAM and EEPROM, all parameter changes are automatically written to the EEPROM
and remain stored there even if the FI is disconnected from the mains supply.
2 =
OFF, no saving in RAM and EEPROM possible (no parameter changes are accepted)
NOTE:
If BUS communication is used to implement parameter changes, it must be ensured
that the maximum number of write cycles (100,000 x) in the EEPROM is not
exceeded.
Pos: 55 0 /Anlei tung en/El ektr onik/FU und Star ter/5 . Par ameter/ Par ameter aufli stung (P000 .. .)/P5 00-P5 99/Par amet er P560 Parameter Speichermode_Ergänzung_01 [SK 2xxE, SK 2xxE-FDS] @ 10\mod_1456908913923_388.docx @ 311240 @ @ 1
PLC: A stored PLC program is also protected by the settings "0" or "2". However,
with the setting "0" the PLC program can also not be loaded or executed.
Pos: 55 1 /Allg emein/ Allg emeing ültig e Module/---------Seitenu mbruc h komp akt --------- @ 13\mod_1476369695906_0.docx @ 2265495 @ @ 1

Table of Contents

Other manuals for Nord Drivesystems NORDAC FLEX SK 230E Series

Related product manuals