Norlake LogiTemp Plus - Typical Set Points for Controller

Norlake LogiTemp Plus
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
26 6/23, 171606 ©2023 Norlake, Inc. All rights reserved.
Typical Set Points For The LogiTemp® Plus Controller
Setting
Definition
Reverse Cycle Defrost
Low Temp
High Temp
tS
Setpoint
-10
35
rFG
Refrigerant
449
449
dty
Defrost Type
rCd
rCd
Edt
Valve Type
rS
rS
SSP
Superheat S.P.
10
10
HoP
Max Suction
150
150
LoP
Min Suction
0
0
LPP
Min Valve Def.
20%
20%
HPP
Max Calve Def.
75%
75%
FoT
Fan on Temp
35
55
Ctd
Coil Temp Diff.
10
10
LLt
Time Lead/Lag
0
0
Ato
Alt Temp Diff.
5
5
Crt
Min Run Time
2
2
Cot
Min Off Time
2
2
Cyr
Refrig, Fan Mode
PEr
PEr
din
Defrost Initiate T.
SCH
SCH
dPd
Defrost Per Day
4
2
Int
Max Interval Def.
360
720
dFS
Defrost Fan State
oFF
oFF
dtP
Defrost Term T.
50
50
dtL
Max Defrost Time
10
10
drn
Drain Time
5
0
Cyd
Defrost Heat Mode
Prm
Prm
Fdt
Fan Cut-in Temp
20
35
Fnt
Max Fan Delay
5
5
Pdt
Pumpdown Time
12
2
bnt
Bond Type
SyC
SyC
HAo
High Temp Offset
10
10
LAo
Low Temp Offset
10
10
LAd
Temp Alarm Delay
45
45
drd
Door Open Alarm
30
30
AU1
Aux 1
diS
diS
A1A
Aux 1 State
CLo
CLo
AU2
Aux 2
diS
SoF
A2A
Aux 2 State
CLo
CLo
AU3
Aux 3
diS
SoF
A3A
Aux 3 State
CLo
CLo
tS2
2nd Room T.
-5
40
Atd
Air Tep Diff.
5
3
CLA
Clear Alarms
-
-
bnd
Bonding
-
-
SA
Smart Acess
diS
diS
dHC
Client Mode
diS
diS