EasyManua.ls Logo

Nortec NHDI - Maintenance Checklist

Nortec NHDI
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
-28-
Maintenance Checklist (p.1 of 2)
Unit Serial #: ________ # of humidifiers: _____ Tag: _____________
Unit type: NHSC / NHDI
Voltage: _____V/___ph Steam output: ____lbs./hr
Customer/Job: _______________ Address: _________________________________________________
Maintenance by: _____________ Date of maintenance:___/___/___
______________________________________________________________________________________
Type of maintenance:
Periodic maintenance, once per week:
- Inspect water and steam installation lines for leaks
- Inspect drain lines for clogging
- Inspect electrical installation for loose cables and damaged components.
- Inspect the humidifier for damage.
Minor servicing, when the yellow LED flashes and display indicates minor maintenance due:
- Carry out periodic inspection items
- Empty the steam cylinder and clean the mineral collector.
Major servicing, when the yellow LED flashes and display indicates major maintenance due:
- Carry out periodic inspection items
- Empty the steam cylinder and clean the mineral collector.
- Dismantle and clean the steam cylinder
- Clean the unit inner chamber
- Inspect the inside components for damage.
Note: Time interval between minor and major are set through rotary switch #2 on the control board.
Cleaning recommendations for the Steam cylinder, mineral collector tank (NHSC Only) and
steam cylinder (NHSC Only) insert:
- Drain unit completely including mineral collector tank drain
- Remove lime collector tank, remove steam cylinder
- Whenever possible, chip off or scrape off any scale coating
- Wash and rinse parts with lukewarm soap water (If components are heavily scaled, place them
in 8% formic acid until the scale has dissolved. Then treat components as previously described.)
Cleaning recommendations for heating elements:
- Wash and rinse heating with lukewarm soap water (If components are heavily scaled, place
them in 8% formic acid until the scale has dissolved. Then treat components as previously described.)
Warning: On no account remove scale coating on the heating element with tools or by striking. This
could damage the heating element.
Cleaning recommendations for internal plumbing components:
- Wipe down components inside the unit with a damp cloth (clean water).
- Severely scaled components should be cleaned using commercially available cleaning and
de-scaling agents.
Warning: Ensure electrical connections remain dry!!!
For more information on cleaning agents and formic acid, review notes in the installation manual.