MG1E-056F1A(A,B)M1
MODEL NAME/
HEATING INPUT
MOTOR
SPEED
EXTERNAL STATIC PRESSURE (IN. W.C.)
0.1 0.2 0.3 0.4 0.5
CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE
MG1E-056F1AAM1
56,000 BTU/Hr
5 - High
4 - Alternate
3 - Med-Hi* 928 45 876 47 829 50
2 - Med-Low 890 47 843 49 790 53 735 56 683 61
1 - Low 798 52 749 55 695 60 629 66
MG1E-070F1A(A,B)M1
MODEL NAME/
HEATING INPUT
MOTOR
SPEED
EXTERNAL STATIC PRESSURE (IN. W.C.)
0.1 0.2 0.3 0.4 0.5
CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE
MG1E-070F1AAM1
70,000 BTU/Hr
5 - High
4 - Alternate
3 - Med-High* 1,212 43 1,178 44 1,148 45 1,114 47 1,079 48
2 - Med-Low 931 56 886 59 836 62 782 66 732 71
1 - Low
MG1E-077F1AAM1
MODEL NAME/
HEATING INPUT
MOTOR
SPEED
EXTERNAL STATIC PRESSURE (IN. W.C.)
0.1 0.2 0.3 0.4 0.5
CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE
MG1E-077F1AAM1
77,000 BTU/Hr
5 - High
4 - Alternate
3 - Med-High* 1,212 47 1,178 48 1,148 50 1,114 51 1,079 53
2 - Med-Low 996 57 960 59 924 62 885 64 848 67
1 - Low
MG1E-090F1AAM1
MODEL NAME/
HEATING INPUT
MOTOR
SPEED
EXTERNAL STATIC PRESSURE (IN. W.C.)
0.1 0.2 0.3 0.4 0.5
CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE
MG1E-090F1AAM1
85,000 BTU/Hr
5 - High
4 - Med-High
3 - Med-Low* 1,188 56 1,154 58 1,119 60 1,091 61 1,054 63
2 - Alternate 1,015 66 978 68 956 70 917 73
1 - Low
NOTES:
1. To comply with government mandated efficiency standards, two openings are required for airflows above 1,600 CFM.
2. Data is shown without filter.
3. Temperature rises in the table are approximate. Actual temperature rises may vary.
4. Individual cells shaded in gray indicate a temperature rise outside of the recommended range.
5. To comply with government mandated efficiency standards, speed settings shaded in gray are not allowed in HEAT mode.
6. The “*” denotes the factory heat and cool setting. If a different motor speed is needed, the appropiate wire from the “HEAT” or “COOL” tap
on the control board must be connected to the desired Tap (1-5) at the motor.
Table 15. Heating Airflow (CFM) & Temperature Rise (°F)