12 HS-NCM Installation Document — P/N 54014:B2 04/25/2014
6.5 Approved Cables and Distances for HS-NCM Applications
The following table shows approved wiring cables that can be used with the HS-NCM and the maximum total distance
allowed for each.
6.6 External Power for HS-NCM Applications
When using the HS-NCM with UL 8th edition panels, UL 9th edition panels where power
can not be applied via the NUP port or when configured as a repeater, a 24 VDC external
power source is required. Where applicable, the external 24 VDC external power source
must share the same ground reference as the NUP port.
Wire Type / Gauge Maximum Distance: Wire Type / Guage Maximum Distance
Aerospace 7131KK / 16 AWG 2000 ft. (609.6 m.) Genesis 4433 / 14 AWG 3,000 ft. (914.4 m)
Belden 5220UM / 16 AWG 1,000 ft. (304.8 m) Genesis 4631 / 18 AWG 3,000 ft. (914.4 m)
Belden 5320UJ / 18 AWG 3,000 ft. (914.4 m) Genesis 4633 / 14 AWG 3,000 ft. (914.4 m)
Belden 5320UM / 18 AWG 3,000 ft. (914.4 m) Genesis 5502 / 16 AWG 1,000 ft. (304.8 m)
Comtran 8696 / 18 AWG 1,000 ft. (304.8 m) Lake Cable SNY141PR-NOT / 14 AWG 1,200 ft (365.8 m)
Comtran 8698 / 14 AWG 1,000 ft. (304.8 m) Pyrotenax 2/16-246T / 16 AWG 425 ft (129.5 m)
Comtran 8706 / 16 AWG 1,000 ft. (304.8 m) Radix CI14A0702-0000-I5000 / 14 AWG 1,500 ft (457.2 m)
Comtran 8709 / 14 AWG 1,000 ft. (304.8 m) Radix CI16A0102-0000-I5000 / 16 AWG 1,600 ft (487.6 m)
Comtran 35777 VitaLink 2C/16 / 16 AWG 850 ft (259.0 m) Shawflex 64220M140118700 / 14 AWG 250 ft (76.2 m)
Draka USA C FLPR-2C/16NS / 16 AWG 1,000 ft. (304.8 m) West Penn AQ225 / 16 AWG 1,000 ft (304.8 m)
Genesis 4050 / 18 AWG 3,000 ft. (914.4 m) West Penn D980 / 18 AWG 2,000 ft (609.6 m)
Genesis 4431 / 18 AWG 2,000 ft. (609.6 m) West Penn D990 / 16 AWG 2,000 ft (609.6 m)
Table 4 Maximum Distance for Approved Cables.