64
INA 15092:I 05/30/01
Option 7 of the Partial System Programming menu allows the user to change the INA mode of operation from Block
Acknowledge to Receiving Unit Mode . Note: If the mode of operation is changed, all nodes in the INA's group must be
reprogrammed for the same operational mode. If an NCS, AFP-300/400 or AFP-200 fire alarm panel is present on the
NOTIFIRENET network, Receiving Unit Mode can not be selected. The NCS, AFP-300/400 and AFP-200 do
not support receiving unit mode at this time.
PRESS 1=PSYS,3=PPRG,4=FPRG,5=REMV,6=PSWD,7=MSG : 1
PRESS 1=NFN,2=KEY,3=CABLE,4=ANN,5=UDACT,6=EXTEQ,7=LOCP : 7
DO@YOU@WANT@TO MODIFY NFPA LISTING? (Y=YES,N=NO) @@@@@@ @@@ : Y
SELECT NFPA LISTING (1=RCV) : 1
DO YOU WANT TO PROGRAM OR REMOVE THIS LISTING? (Y=PRG,N=RMV) : N
7=LOCP - Local Parameters D }X1X7X
6=EXTEQ - External Equipment D }X1X6X
Option 6 of the Partial System Programming menu allows the user to change any optional features associated with the CRT
monitor, printer(s), Page-1 interface, or modem interface.
Terminal Supervision: Electrical supervision of the CRT monitor. Unless terminal supervision is selected, the CRT will not
beep (i.e. no bell characters will be sent) when unacknowledged troubles or unacknowledged alarms are present.
Printer Monitoring: The INA will monitor the printer's Ready/Busy line for off-line, out of paper, or buffer full error
conditions. This option only functions for PRN or Keltron printers.
Pager: The pager must be enabled when a compatible pager is connected to the auxiliary printer port.
Modem: If selected, the following remote device (CRT) functions are inhibited: ACK STEP, SIGNAL SILENCE, SYSTEM
RESET, PROGRAMMING and ALTER STATUS. This option must be employed when a modem is used to receive signals
from an off-premise device. See the TPI-232 manual.
PRESS 1=PSYS,3=PPRG,4=FPRG,5=REMV,6=PSWD,7=MSG : 1
PRESS 1=NFN,2=KEY,3=CABLE,4=ANN,5=UDACT,6=EXTEQ,7=LOCP : 6
DO@YOU@WANT@TO@CHANGE@THE@TERMINAL@SUPERVISION?@(Y=YES,N=NO)@@@@@@@@@@@ : Y
DO@YOU@WANT@THE@TERMINAL@SUPERVISION@ENABLED?@(Y=YES,N=NO)@@@@@@@@@@@@ : Y
DO@YOU@WANT@TO@CHANGE@THE@PRINTER@MONITORING?@(Y=YES,N=NO)@@@@@@@@@@@@ : Y
DO@YOU@WANT@THE@PRINTER@MONITORING@ENABLED?@(Y=YES,N=NO)@@@@@@@@@@@@@@@@: Y
DO@YOU@WANT@TO@CHANGE@THE@PAGER@PROGRAMMING?@(Y=YES,N=NO)@@@@@@@@@@@@@@ :@Y
DO@YOU@WANT@THE@PAGER@ENABLED?@(Y=YES,N=NO)@@@@@@@@@@@@@@@@@@@@@@@@@@@ :@Y
DO YOU WANT TO CHANGE THE MODEM PROGRAMMING? (Y=YES,N=NO) : Y
DO YOU WANT THE MODEM ENABLED? (Y=YES,N=NO) : Y