Installation & Operation Manual FTG
4
FTG boilers are factory set to operate with Natural Gas; BEFORE OPERATING
WITH PROPANE, the boiler must be converted using the appropriate Natural Gas to
LP Conversion Kit see below; each kit comes with conversion instructions. Failure to
properly convert the unit to safely operate with Propane will cause severe boiler failure,
resulting in property damage, serious injury or death.
ATTENTION: LIQUEFIED PETROLEUM (LP) PROPANE
Liquefied Petroleum (LP) propane gas is heavier than air; therefore, it is imperative that your boiler is not
installed in a pit or similar location that will permit heavier than air gas to collect. Local Codes may require
boilers fueled with LP gas be provided with an approved means of removing unburned gases from the room.
Check your local codes for this requirement.
Natural Gas to LP Conversion Kit
Model
Kit Part Number
LP-Orifice
FTG 600-1400
85418-1
N/A
FTG 2000-2400
85758-1
N/A
Exhaust Vent / Air-Inlet Piping
The FTG is certified as a “Category IV” boiler, and requires a “Special Venting System”
designed for pressurized venting. The exhaust gases must be piped directly to the
outdoors using the vent materials and rules outlined in these instructions. Failure to
follow these instructions will result in serious injury or death.