High Altitude Operation
The FTG is designed to operate at its maximum listed capacity in installations located at 0-2000 ft above Sea
Level. Since the density of air decreases as elevation increases, maximum specified capacity should be de-rated
for elevations above 2000 ft [610 m] in accordance with Table 2-3.
Table 2-3 De-rate % for High Altitudes
Notes:
1
Canada: Altitudes between 2000 & 4500 ft. [610 &1372 m], de-rate by 10%. Consult local authorities for de-rating for
altitudes above 4500ft [1372 m].
2
USA: De-rate capacity by 4% for every 1000 ft [305 m], if altitude is above 2000 ft [610 m].
Combustion – At elevations above 2000 feet, the combustion of the boiler must be
checked with a calibrated combustion analyzer to ensure safe and reliable operation. It is
the Installers responsibility to check the combustion and to adjust the combustion
in accordance with Section 9.0. Failure to follow these instructions may result in
property damage, serious injury, or death.