Part 0. General Safety information
NTI boilers are factory set to operate
with Natural Gas.
BEFORE OPERATING WITH PROPANE
the boiler must be converted to
Propane using this kit.
Use the procedures outlined in these
instructions to fully complete the
Natural Gas to LP conversion for
models 085, 110, 150, 199, 110C,
150C and 199C.
Kit Contents:
- Natural to LP Conversion Instructions nr. 1
- LP Conversion Label nr. 1
- LP-Mixer w. Diaphragm (Table 1) nr. 1
- Gasket for gas pipe nr. 2
Model
Polidoro code
(MIXER data plate)
LP diaphragm
Ø in (mm)
085, 110, and 110C
350_0944_02
or
350_0944_03
6.4 mm
150 and 150C
350_0921_02
or
350_0921_03
199 and 199C
350_0922_02
or
350_0922_03
6.9 mm
Table 1 - LP Mixer and Gas diaphragm
Data plate
LP diaphragm
IF THE KIT CONTENTS DO NOT MATCH
THOSE SPECIFIED FOR YOUR BOILER
MODEL (SEE TABLE 1), DO NOT
PROCEED WITH INSTALLING THE
LP-CONVERSION KIT, AND DO NOT
OPERATE THE BOILER - CONTACT NTI
FOR ASSISTANCE.